VII. MICROPROCESSOR CONTROL (continued)

VII. n - SETTING THE DEFROST LOCKOUTS:

The defrost lockout parameters allow the customer to prevent the unit from going into a defrost cycle for two hours during a set timeframe. Customers can set up to four defrost lockout parameters. They are all programmed the same way. The parameters will be set for the time the lockout is to start. The controller automatically calculates 2 hours from that setting. The options are similar to the 24-hour clock settings and are in 30-minute increments. Each of the lockout parameters covers 6 hours of the 24-hour clock. Note: The 24-hour clock must be set for this feature to operate at the correct time of day. See Setting the 24-Hour Clockon page 10.

OFF

OFF

OFF

OFF

020 = 2:00 a.m.

080

= 8:00 a.m.

140 = 2:00 p.m.

200

= 8:00 p.m.

023 = 2:30 a.m.

083

= 8:30 a.m.

143 = 2:30 p.m.

203

= 8:30 p.m.

030 = 3:00 a.m.

090

= 9:00 a.m.

150 = 3:00 p.m.

210

= 9:00 p.m.

033 = 3:30 a.m.

093

= 9:30 a.m.

153 = 3:30 p.m.

213

= 9:30 p.m.

040 = 4:00 a.m.

100

= 10:00 a.m.

160 = 4:00 p.m.

220

= 10:00 p.m.

043 = 4:30 a.m.

103

= 10:30 a.m.

163 = 4:30 p.m.

223

= 10:30 p.m.

050 = 5:00 a.m.

110 = 11:00 a.m.

170 = 5:00 p.m.

230

= 11:00 p.m.

053 = 5:30 a.m.

113 = 11:30 a.m.

173 = 5:30 p.m.

233

= 11:30 p.m.

060 = 6:00 a.m.

120

= 12:00 p.m.

180 = 6:00 p.m.

240* = 12:00 a.m.

063 = 6:30 a.m.

123

= 12:30 p.m.

183 = 6:30 p.m.

243* = 12:30 a.m.

070 = 7:00 a.m.

130

= 1:00 p.m.

190 = 7:00 p.m.

010

= 1:00 a.m.

073 = 7:30 a.m.

133

= 1:30 p.m.

193 = 7:30 p.m.

013

= 1:30 a.m.

080 = 8:00 a.m.

140

= 2:00 p.m.

200 = 8:00 p.m.

020

= 2:00 a.m.

 

 

 

* Denotes not available.

A lockout cannot be programmed to start at 12:00 a.m. or 12:30 a.m. due to conflicts with other internal programs. The defrost lockouts cannot be programmed to run back-to-back. For example, if dL1 is set to 080, then a defrost cycle would be locked out from 8:00 a.m. to 10:00 a.m. Because of the dL1 setting the dL2 parameter would not let the user choose a lockout start time before 10:30 a.m. All lockouts are preset at the factory to OFF.

Follow the instructions to enter the customer access code on page 7. When the control

displays Thermostat Set High, press the down arrow keyuntil the control the

control display reads

or

. Press the set button SET .

The display will show

Off. Press the arrow keys to set the start time.

When the correct time is displayed, press the set button SET .

The display will then read Thermostat Set Point High.

You can press the up or down arrow keys to scroll to the next parameter

or wait 30 seconds for the control to return to normal operation.

-13-