IX. TROUBLESHOOTING GUIDE

PROBLEM

 

POSSIBLE CAUSE/REMEDY

1. Condensing unit fails to start - no hum.

1.

Line Disconnected - Reconnect

 

2.

Fuse - Replace Fuse

 

3.

Overload Protection - Determine Reason & Correct,

 

 

Replace If Necessary

2. Condensing unit fails to start - hums but

1.

Improperly Wired - Check Wiring Against Diagram

trips on overload protector.

2.

Low Voltage - Determine Reason & Correct

 

3.

Starting Capacitor Defective - Determine Reason & Replace

 

4.

Relay Not Closing - Determine Reason & Correct,

 

 

Replace If Necessary

 

5.

Compressor Motor Has Winding Open Or Shorted - Replace

 

 

Compressor

 

6.

Internal Mechanical Trouble In Compressor - Replace

 

 

Compressor

3. Condensing unit starts, but fails to switch

1.

Improperly Wired - Check Wiring Against Diagram

off of “start” winding.

2.

Low Voltage - Determine Reason & Correct

 

3.

Relay Failing To Open - Determine Reason & Correct,

 

 

Replace If Necessary

 

4.

Run Capacitor Defective - Determine Reason & Replace

 

5.

Excessively High Discharge Pressure - Check Disharge

 

 

Shut-Off Valve, Or Insufficient Cooling On Condenser

 

6.

Compressor Motor Has Winding Open Or Shorted - Replace

 

 

Compressor

 

7.

Internal Mechanical Trouble In Compressor - Replace

 

 

Compressor

4. Condensing unit starts and runs, but short

1.

Additional Current Passing Through Overload Protector -

cycles on overload protector.

 

Check Wiring Diagram. Check For Added Fan Motors,

 

 

Pumps, etc., Connected To Wrong Side Of Protector

2.Low Voltage To Unit (or unbalanced if three phase) - Determine Reason & Correct

3.Overload Protector Defective - Check Current - Replace Protector

4.Run Capacitor Defective - Determine Reason & Replace

5.Excessive Discharge Pressure - Check Ventilation, Restrictions In Cooling Medium, Restrictions in Refrigeration System

6.Suction Pressure Too High - Check For Possibility Of Misapplication. Use Stronger Unit

7.Compressor Too Hot (return gas) - Check Refrigerant Charge (fix leak) Add If Necessary

8.Compressor Motor Has Winding Shorted - Replace Compressor

5.Condensing unit runs but short cycles on... 1. Overload Protector - See #4 Above

2.Thermostat - Differential Set Too Close, Widen

3.High Pressure “Cut-Out” Due To:

a)Insufficient Air or Water Supply - Check Air or Water Supply To Condenser, Correct

b)Overcharge - Reduce Refrigerant Charge

c)Air In System - Purge

4.Low Pressure “Cut-Out” Due To:

a)Liquid Line Solenoid Leaking - Replac e

b)Compressor Valve Leak - Replace

c)Undercharge - Fix Leak, Add Refrigerant

d)Restriction In Expansion Device - Replace Device