TRENDnet Series 300 manual CONTROL FEATURES continued, DIP Switch Settings

Models: Series 300

1 18
Download 18 pages 59.02 Kb
Page 14
Image 14
CONTROL FEATURES (continued)

CONTROL FEATURES (continued)

OPTIONAL PROGRAMMABLE ENGINE EXERCISER (Accessory 11CD)

The optional programmable engine exerciser provides seven days of different exercise periods. The timer is connected and mounted below the controller. A permanent backup battery maintains the setting; when power is lost to timer, output switch deenergizes.

DIP Switch Settings

FUNCTION

S1 DIP

 

 

 

S2 DIP

 

 

 

SWITCH

 

 

 

SWITCH

 

 

 

 

 

 

 

 

 

 

Opt. Timer

Actuator

 

 

 

 

 

 

 

 

Actuator

 

 

 

 

 

5

 

 

 

 

 

7

 

 

 

 

Enabled

7 off

 

 

 

 

 

 

5 off

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Opt. Timer

Actuator

 

 

 

 

 

 

 

 

Actuator

 

 

 

 

 

 

 

 

 

 

7

 

 

 

 

5

 

Disabled

7 off

 

 

 

 

5 on

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Exercise

Actuator

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

without

 

 

 

8

 

 

 

 

 

 

 

 

 

 

Load

8 off

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Exercise

Actuator

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

with

 

 

 

 

8

 

 

 

 

 

 

 

 

 

 

8 on

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Load

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Shaded DIP switches are standard factory settings.

The Accessory 11CD Programmable Engine Exerciser incorporates a 7 day time base, and therefore, each day of the week can be uniquely programmed to test the engine generator set either with or without load. The proper controller settings must be made to determine whether or not the test will be conducted with or without load (refer to page 5–1 for proper selection). For convenience, Block Programming is also provided, whereby up to seven days can be grouped together if the ON and OFF times are the same.

See next page for instructions on setting the timer.

5--2

Page 14
Image 14
TRENDnet Series 300 CONTROL FEATURES continued, OPTIONAL PROGRAMMABLE ENGINE EXERCISER Accessory 11CD, DIP Switch Settings