TESTING & SERVICE (continued)
MANUAL LOAD TRANSFER
This procedure will manually transfer the load if the controller is disconnected.
!
Do not manually operate the transfer switch until both power sources are disconnected: open both circuit breakers.
1.Open normal and emergency source circuit breakers.
2.Use the maintenance handle to manually operate transfer switch to the opposite source. See page
3.If the transfer switch is in the Emergency position manually start the engine generator and then close the emergency source circuit breaker.
|
|
|
|
|
| ||
Note the control features that are activated or furnished |
|
|
|
|
|
| |
| ! |
|
|
|
| ||
|
|
|
|
| |||
on the switch and review their operation. Refer to Section |
|
|
|
|
| ||
|
|
|
|
|
| ||
5, Control Features. |
|
| Proceed with care! |
| |||
|
|
| The automatic transfer switch is energized. |
| |||
| Table | Shooting Checks. |
|
|
|
| |
|
|
|
|
| |||
PROBLEM | CHECK IN NUMERICAL SEQUENCE |
| |||||
1 OPERATION |
| 2 |
|
| 3 VOLTAGE |
| |
|
|
|
|
| |||
Hold the TRANSFER SWITCH | Starting control must be in |
|
|
|
| ||
the TRANSFER SWITCH TEST | TEST button 15 sec. or the | automatic position. Batteries |
|
|
|
| |
button is pressed and held for | outage must be long enough | must be charged and |
|
|
|
| |
15 seconds or when the | to allow for the 1 or 3 sec. | connected. Check wiring to |
|
| — |
| |
normal source fails. | Momentary Normal Source | engine starting contacts. |
|
|
|
| |
| Outage Delay plus engine |
|
|
|
|
|
|
| cranking and starting time. |
|
|
|
|
|
|
|
|
|
|
| |||
Transfer switch does not | Wait for Transfer to Emergen- | Generator output circuit | Voltmeter should read at |
| |||
transfer the load to | cy Delay (0 to 5 min.) to time | breaker must be closed. | least 90% of nominal phase to |
| |||
emergency source after the | out. For immediate transfer, | Generator frequency must be | phase voltage between |
| |||
press the BYPASS TIME | at least 57 Hz. | transfer switch terminals EA |
| ||||
| DELAY button. If Motor Load |
|
| and EC (or EL1 and EL2 for 2 |
| ||
| Transfer is active, wait for in- |
|
| pole switches). * |
| ||
| phase condition (see below). |
|
| * These are factory settings. |
| ||
|
|
|
|
|
| ||
Transfer switch does not | Wait for Retransfer to Normal |
|
| Voltmeter should read at least |
| ||
transfer the load to normal | Delay (1 sec. to 30 min.) to |
|
| 90% of nominal phase to |
| ||
source when normal returns | time out. For immediate re– |
|
| phase voltage between |
| ||
or when TRANSFER SWITCH | transfer, press BYPASS TIME |
| — | transfer switch terminals NB |
| ||
TEST button is released. | DELAY button. If Motor Load |
|
| and NC, NC and NA, and NA |
| ||
| Transfer is active, wait for in- |
|
| and NB (or NL1 and NL2 for 2 |
| ||
| phase condition (see below). |
|
| pole switches). |
| ||
|
|
|
|
|
|
| |
Wait for the 5 minute | Starting control must be in |
|
|
|
| ||
load retransfer to the normal | Unloaded Running Delay to | automatic position. |
|
| — |
| |
source. | time out. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Trouble-Shooting the Motor Load Transfer Feature (refer to page 5–3)
Use extreme caution when using a meter to measure voltages in the following steps. Do not touch power terminals; shock, burns, or death could result !
3.Press and hold TRANSFER SWITCH TEST button. The load should transfer to emergency source when meter needle is near 0 volts. If transfer does not occur, Motor Load Transfer feature is not operating.
4.Release the Transfer Switch Test button. The load should retransfer back to the normal source after the
1.Connect a voltmeter (set for twice system
2.Manually start generator. Voltmeter needle should sweep back and forth at a regular rate between 0 and about twice system voltage.
should occur when the needle is near 0 volts. If retransfer does not occur after the time delay, the Motor Load Transfer feature is not operating.
5.For immediate retransfer, press the BYPASS TIME DELAY button. Then disconnect the voltmeter.
If the problem is isolated to circuits on the controller or the transfer switch, call your local ASCO Power Technologies sales office. Furnish Serial No., Bill of Material (BOM) No., & Catalog No. from the transfer switch nameplate.