SECTION 3 TESTING & SERVICE

PREVENTIVE MAINTENANCE

DISCONNECTING THE CONTROLLER

Reasonable care in preventive maintenance will insure high reliability and long life for the automatic transfer switch.

Operate the switch at least once a month. Perform this four step Electrical Operation Test. This is a test with load transfer.

TRANSFER SWITCH TEST

BYPASS TIME DELAY SET ENGINE EXERCISER

Press for 15 Seconds

Press until light FLASHES

 

 

Transfer Switch Test

1.Press and hold the door-mounted TRANSFER SWITCH TEST button until the engine starts and runs. This should happen within 15 seconds.

2.The transfer switch will operate to the Emergency position. If the Transfer To Emergency Delay is used, the transfer will occur after a time delay (up to 5 minutes). For immediate transfer press BYPASS TIME DELAY button.

3.The Transfer Switch will operate back to the Normal position after the Retransfer To Normal Delay (up to 30 minutes). For immediate retransfer press BYPASS TIME DELAY button.

4.Unloaded Running (Engine Cooldown) Delay allows engine to run unloaded for 5 minutes.

Clean and inspect the switch once a year. De-energize all sources, then brush and vacuum away any excessive dust accumulation. Remove the transfer switch barriers and check contact condition. Replace contacts when pitted or worn excessively. Reinstall the barriers carefully.

Maintain transfer switch lubrication. The transfer switch has been properly lubricated, and under normal operating conditions no further lubricating is required. Renew factory lubrication if the switch is subjected to severe dust or abnormal operating conditions. Relubricate the operator if TS coil is replaced. Order lubrication kit 75-100.

Replacement parts. Replacement parts are available in kit form. When ordering parts provide the Serial No. and Catalog No. from the transfer switch nameplate. Contact your local ASCO Power Technologies sales office.

3--1

The harness disconnect plugs are furnished for repair purposes only and should not have to be unplugged. If the controller must be isolated, follow these steps carefully.

Disconnecting the Plugs

!

Do not unplug the controller until step

1a. or 1b. below is completed.

1.Observe the position of the transfer switch.

a.If the transfer switch is in the Normal position, place standby engine starting control in the off position. Then open the emergency source circuit breaker.

b.If the transfer switch is in the Emergency position, open the normal source circuit breaker. Place the engine starting control in the test or run position.

2.Separate the quick disconnect plugs by squeezing the latches. Do not pull on the harness wires.

3.Label, remove, and tape the signal wires connected to the engine start terminals on the transfer switch: TB1 and TB3, or TB1 and TB2.

Reconnecting the Plugs

!

Do not reconnect the controller until step 1a. or 1b. and 2 below are completed.

1.Observe the position of the transfer switch.

a.If the transfer switch is in the Normal position, be sure that the standby engine starting control is still in the off position. The emergency source circuit breaker still should be open.

b.If the transfer switch is in the Emergency position, normal source circuit breaker still should be open.

2.Reconnect the signal wires connected to the appropriate engine start terminals on the transfer switch. See Section 1, Engine Starting Contacts.

3.The harness plugs and sockets are keyed. Carefully align the plugs with the sockets and press straight in until both latches click.

4.Restore the opposite source as follows:

a.If the transfer switch is in the Normal position, place the standby engine starting control in the automatic position. Then close the emergency source circuit breaker.

b.If the transfer switch is in the Emergency position, close the normal source circuit breaker. The load will be automatically retransferred to the normal source after the Retransfer to Normal Delay. For immediate retransfer, press BYPASS TIME DELAY button. Place the engine starting control in the automatic position.

Page 9
Image 9
TRENDnet Series 300 manual Testing & Service, Preventive Maintenance

Series 300 specifications

TRENDnet Series 300 is a powerful lineup of networking devices designed to deliver robust performance and high-speed connectivity for various applications. With its focus on both home and small office environments, the Series 300 incorporates advanced technologies to ensure seamless connectivity and enhanced network management.

One of the primary features of the TRENDnet Series 300 is its support for the latest wireless standards. Equipped with 802.11ac technology, these devices provide significant improvements in speed and range compared to previous generations. Users can experience wireless speeds up to 1300Mbps, making it ideal for streaming high-definition content, online gaming, and large file transfers.

Additionally, the Series 300 boasts dual-band capabilities, allowing users to connect to both 2.4GHz and 5GHz frequency bands. This flexibility helps to reduce interference and ensures stable connections for multiple devices simultaneously. The dual-band feature is particularly beneficial in crowded environments, where numerous devices compete for bandwidth.

Security is paramount in any networking solution, and TRENDnet Series 300 devices offer robust security protocols to safeguard users' data. With support for WPA/WPA2 encryption, users can ensure their wireless networks are protected against unauthorized access. Furthermore, many models in this series integrate advanced security features such as a built-in firewall and guest network options, providing an extra layer of protection.

Another notable characteristic is the intuitive user interface, which simplifies the setup and management of network configurations. Users can easily access and modify settings through a user-friendly web interface or a mobile application. This ease of management makes it accessible even for users with limited technical expertise.

The Series 300 is also designed with versatility in mind, featuring multiple Ethernet ports for wired connections. This is beneficial for devices that require a stable network connection, such as gaming consoles and smart TVs. Additionally, Power over Ethernet (PoE) capabilities allow the devices to power compatible network devices, reducing cable clutter.

Finally, TRENDnet's commitment to reliability is evident in the build quality of the Series 300. These devices are engineered for long-lasting performance and efficiency, making them a trustworthy choice for both personal and professional networking needs. Overall, the TRENDnet Series 300 series stands out as a comprehensive networking solution, incorporating speed, security, and ease of use into its design.