Specifications (Hardwired Models)
HARDWIRED MODELS: | APS 2012 | APS2424 |
Weight: | 38.0 lbs. | 41.0 lbs. |
INVERTER |
|
|
Continuous power (@ 20° C): | 2000 W | 2400 W |
Surge power (5 seconds): | 4000 W | 4800 W |
Efficiency (Full Load): | 90% | 90% |
Minimum DC Fuse Rating: | 500A | 300A |
DC Input Current @ Nominal V DC |
|
|
Full Load | 192 A | 112 A |
No Load | 2.5 A* | 1.5 A* |
Nominal Input Volts: | 12 VDC | 24 VDC |
DC Input Voltage Range: | ||
Nominal Output Volts: | 120 VAC ±5% | 120 VAC ±5% |
Nominal Output Frequency: | 60 Hz ±.3% | 60 Hz ±.3% |
BATTERY CHARGER |
|
|
Charging Capacity DC: | 60 A | 30 A |
Maximum Cable Length | 1 ft. | 3 ft. |
Acceptance Volts VDC: | Selectable | Selectable |
| 14.4 V**/14.2 V Wet**/Gel | 28.8 V**/28.4 V Wet**/Gel |
Float Volts VDC (w/gel): | 13.3 V (13.6 V) | 26.6 V (27.2 V) |
Input Voltage AC: | 120 V | 120 V |
Input Current AC: | 16 A | 16 A |
LINE VAC OPERATION |
|
|
Minimum Input AC Volts: | Selectable 75**,85, 95, or 105 VAC Selectable 75**,85, 95, or 105 VAC | |
Maximum Input AC Volts |
|
|
(Continuous, Charger at Maximum): | Selectable 135** or 145 VAC | Selectable 135** or 145 VAC |
Maximum Input Current |
|
|
(Continuous, Charger at Maximum): | 32 A | 36 A |
Input Frequency: | 60 Hz ±10% | 60 Hz ±10% |
Maximum Output AC (Continuous) | 16.7 A | 20 A |
Automatic Transfer Time: |
HARDWIRED MODELS (Cont.): | APS 2448 | APS3636VR | |
Weight: | 38.0 lbs. | 56.9 lbs. | |
INVERTER |
|
|
|
Continuous power (@ 20° C): | 2400 W | 3600 W | |
Surge power (5 seconds): | 4800 W | 7200 W | |
Efficiency (Full Load): | 90% | 89% | |
Minimum DC Fuse Rating: | 300A | 300A | |
DC Input Current @ Nominal V DC |
|
|
|
Full Load | 56 | A | 114 A |
No Load | 1.5 A* | 1.7 A* | |
Nominal Input Volts: | 48 VDC | 36 VDC | |
DC Input Voltage Range: | |||
Nominal Output Volts: | 120 VAC ±5% | 120 VAC ±5% | |
Nominal Output Frequency: | 60 | Hz ±.3% | 60 Hz ±.3% |
BATTERY CHARGER |
|
|
|
Charging Capacity DC: | 15 | A | 30 A |
Maximum Cable Length | 12 ft. | 4.5 ft. | |
Acceptance Volts VDC: | Selectable | Selectable | |
| 57.6 V**/56.8 V Wet**/Gel | 43.2 V**/42.6 V Wet**/Gel | |
Float Volts VDC (w/gel): | 53.2 V (54.4 V) | 39.9 V (40.8 V) | |
Input Voltage AC: | 120 V | 120 V | |
Input Current AC: | 16 | A | 24 A |
LINE VAC OPERATION |
|
|
|
Minimum Input AC Volts: | Selectable 75**,85, 95, or 105 VAC Selectable 75**,85, 95, or 105 VAC | ||
Maximum Input AC Volts |
|
|
|
(Continuous, Charger at Maximum): | Selectable 135** or 145 VAC | Selectable 135** or 145 VAC | |
Maximum Input Current |
|
|
|
(Continuous, Charger at Maximum): | 33 | A | 54 A*** |
Input Frequency: | 60 | Hz ±10% | 60 Hz ±10% |
Maximum Output AC (Continuous) | 20 | A | 30 A |
Automatic Transfer Time: |
*Load sense can reduce this to 1/30 of the listed current. **Factory default setting. ***When AVR is boosting incoming current.
15