Brownout correction
Maintains continuous operation without using battery power during brownout / undervoltage conditions to 156V AC, increasing output within 2% of selected nominal
LEDS ALARMS & SWITCHES
Front panel LEDs
6 LED DISPLAY: line power, bypass, inverter, charger, output AC and battery operation.
SELECTABLE LCD DISPLAY: input/output voltage, Hz, battery voltage and charge level and detailed warnings regarding all major UPS functions.
Alarms
Switches
Includes main power off/on switch, plus 2 switches to set and execute scrollable LCD functions
SURGE / NOISE SUPPRESSION
AC surge | 1320 joules |
suppression |
|
|
|
AC suppression | Instantaneous |
response time |
|
|
|
EMI / RFI AC noise | Yes |
suppression |
|
|
|
PHYSICAL |
|
Shipping weight (lbs) | 327.56 |
|
|
Shipping weight (kg) | 147.4 |
|
|
Unit weight (lbs) | Power Module 54.8 lbs. (59.8 lbs w/SUPDMB710HW); Battery Pack: 158.73 lbs. |
|
|
Unit weight (kg) | Power Module: 24.66kg (26.91kg w/SUPDMB710HW), Battery Pack: 71.43kg |
|
|
Unit Dimensions | Power Module 5.14 x 17.5 x 25 (30.25 in. depth w/SUPDMB710HW), Battery Pack 5.16 x 17.5 x 2 |
(HWD/in) |
|
|
|
Unit Dimensions | Power Module 13.1 x 44.5 x 63.5 (76.8 cm depth w/SUPDMB710HW); Battery Pack 13.1 x 44.5 x 63.5 |
(HWD/cm) |
|
|
|
Material of | Steel |
construction |
|
|
|
Form factors | Rack (6U) |
supported |
|
|
|
Cooling method | |
|
|
Battery Access | User replaceable, hot swappable external battery pack |
|
|
ENVIRONMENTAL |
|
Relative Humidity | 0 to 95%, |
|
|
Storage Temperature | +5 to +122 degrees Fahrenheit |
|
|
Operating | +32 to +104 degrees Fahrenheit |
Temperature |
|
|
|
COMMUNICATIONS |
|
Network monitoring | Includes 2 |
port |
|
|
|
Software and cabling | Includes PowerAlert UPS monitoring software for all common network and standalone operating systems. Cabling |
included | included. |
|
|
SNMP compatibility | |
|
|
WatchDog | Yes, compatible with Tripp Lite's Watchdog system service to restore operation to locked equipment through soft reboot |
compatibility | of application / OS or hard power off/on reboot of connected equipmentideal for unattended kiosk applications |
|
|
LINE / BATTERY TRANSFER
Transfer time from line power to battery mode
Low voltage transfer to battery power
Zero transfer time:
Maintains continuous operation during undervoltages as low as 156V AC. Below this point, output is maintained utilizing battery reserves.