Maintains continuous operation through blackouts, voltage fluctuations and surges with zero transfer time
Removes harmonic distortion, electrical impulses, frequency variations and other hard to solve power problems
10,000VA/8,000W power capacity with hardwire input/output connections
Accepts input voltages between 156 and 276, regulating output within 2% of selectable 200/208/220/230/240V AC output
Standard included 3U battery pack provides 10 minutes runtime at half load (5,000VA) and 4 minutes at full load (10,000VA)
Expandable runtime with multiple external battery packs, sold separately
Innovative design makes unit adaptable for rackmount, tower, or stacking applications
Power module and battery pack require only 3 rack spaces each (6U total rack space usage)
DB9 serial port for network interface; SNMP compatible
Slot for optional SNMP/Web card (part# SNMPWEBCARD)
PowerAlert unattended shutdown software and 6 ft. network cable included
Fault tolerant
Detachable hardwired PDU with manual bypass switch enables
Diagnostic LEDs and LCD provide complete overview of operating conditions, UPS status and more
Mounting hardware included
Includes RJ11 EPO (emergency power off) port and interconnection cable
2 year manufacturers product warranty
$250,000 Ultimate Lifetime connected equipment insurance
Specifications
SYSTEM OVERVIEW
Voltage compatibility | 208V AC (200/208/220/230/240V) |
|
|
Frequency | 50/60Hz |
compatibility |
|
|
|
OUTPUT |
|
Output VA | 10000 |
|
|
Output watts | 8000 |
|
|
Output nominal | 208V AC (200/220/230/240V) |
voltage |
|
|
|
Output voltage | Maintains pure sine wave output at all times, regulated within 2% of selected nominal output voltage, less than 5% total |
regulation | harmonic distortion |
|
|
Output frequency | Regulates line frequency to 50/60Hz +/- 0.05Hz |
regulation |
|
|
|
Outlet quantity / type | Hardwire via detachable distribution module |
|
|
INPUT |
|
Maximum input amps | 46.7A (200V), 44.9A (208V), 42.4A (220V), 40.6A (230V), 38.9A (240V) max. |
|
|
Input connection type | Hardwire via detachable distribution module |
|
|
BATTERY |
|
Full load runtime | Included batteries — 4 min (10,000VA) |
|
|
Half load runtime | Included batteries — 10 min (5,000VA) |
|
|
Expandable battery | Supports extended runtime with optional external battery packs |
runtime |
|
|
|
DC system voltage | 240V DC |
|
|
Typical battery | |
lifespan |
|
|
|
Battery recharge rate
Less than 8 hours to 90% (included battery set only)
VOLTAGE REGULATION
Voltage regulation description
Overvoltage correction
Maintains continuous operation without using battery power during overvoltages to 276V AC, reducing output within 2% of selected nominal