Recommended

120/208V AC (3-Phase, 4 Wire, wye)

Electrical Service

 

 

 

BATTERY

 

Full load runtime

Included internal batteries: 17 min. (16,000 watts). Runtime can be extended with additional internal battery packs (model #

 

SURBC2030).

 

 

Half load runtime

Included internal batteries: 42 min. (8,000 watts). Runtime can be extended with additional internal battery packs (model #

 

SURBC2030).

 

 

Expandable

Supports extended runtime with optional internal battery packs (model # SURBC2030). Accepts 3 additional internal

battery runtime

battery packs. Standalone external battery module (SUBF2030) also available.

 

 

DC system voltage

240V DC

 

 

Typical battery

3 - 6 years, depending on usage

lifespan

 

 

 

Battery recharge

2 - 4 hours to 90%

rate

 

 

 

VOLTAGE REGULATION

Voltage regulation description

Overvoltage correction

Brownout correction

On-line, double-conversion process gives this UPS the ability to maintain output voltage within +/-2% of nominal voltage at all times

Maintains continuous operation without using battery power during overvoltages to 144 / 250V AC (3-Phase, 4-Wire, wye), reducing output within 2% of nominal

Maintains continuous operation without using battery power during brownout / undervoltage conditions to 88 / 166V AC (3-Phase, 4-Wire, wye)

LEDS ALARMS & SWITCHES

Front panel LEDs

7 LED DISPLAY: AC input, bypass input, AC-DC charger, DC-AC inverter, AC output, bypass operation and battery

operation. SELECTABLE LCD DISPLAY: indicates a wide range of UPS operational and fault/warning conditions including operational mode, alarm/shutdown conditions, input/output voltage/frequency, battery voltage, load percentage and more.

Alarms

Switches

Alarms warn against a variety of operational conditions: low battery, overload, shutdown, bypass and more

"ON" button turns UPS's inverter ON. "OFF" button turns UPS's inverter OFF. "Select" Button browses through items displayed on LCD screen. "Enter" button selects items displayed on LCD screen. "Select" and "Enter" buttons used simultaneously mute UPS alarms. "Battery Start" Switch cold starts the inverter. "Emergency Power Off" button turns UPS output OFF and disables Bypass output. "Manual Bypass" switch bypasses the UPS's inverter during maintenance.

SURGE / NOISE SUPPRESSION

AC surge

480 joules

suppression

 

 

 

AC suppression

Instantaneous

response time

 

 

 

EMI / RFI AC noise

Yes

suppression

 

 

 

PHYSICAL

 

Shipping weight

1152

(lbs)

 

 

 

Shipping weight

523

(kg)

 

 

 

Shipping

61.5 x 31 x 44.5

Dimensions

 

(HWD/in)

 

 

 

Shipping Dimensions (HWD/cm)

156.2 x 78.7 x 113

Unit weight (lbs)

Unit weight (kg)

Unit Dimensions (HWD/in)

935

424

48.5 x 19.3 x 36

Page 3
Image 3
Tripp Lite SU20K3/3XR5 warranty Battery, Voltage Regulation, Leds Alarms & Switches, Surge / Noise Suppression, Physical

SU20K3/3XR5 specifications

The Tripp Lite SU20K3/3XR5 is a highly efficient and reliable uninterruptible power supply (UPS) designed specifically for critical infrastructure, safeguarding sensitive electronic equipment from power disturbances. Providing 20 kVA capacity, this robust UPS system is an ideal solution for data centers, communication systems, and industries requiring continuous power availability.

One of the standout features of the SU20K3/3XR5 is its advanced double-conversion technology. This allows the UPS to continuously condition incoming power, converting AC to DC and then back to clean AC. This process ensures that output power is free from spikes, surges, and other electrical noise that could potentially damage connected devices. Consequently, the UPS not only provides power in the event of an outage but also enhances the overall reliability of the electrical environment.

The unit is equipped with a high-efficiency inverter and rectifier, contributing to reduced energy consumption and lower operational costs. It offers peak efficiency of up to 95%, which is beneficial in promoting environmentally friendly practices while ensuring system longevity. The SU20K3/3XR5 also features a wide input voltage range, making it adaptable to varied power environments.

Another significant characteristic of the Tripp Lite SU20K3/3XR5 is its scalability. It can seamlessly be paralleled with additional units for increased capacity or redundancy, catering to growing infrastructure needs. This scalability reinforces enhanced availability and provides room for future upgrades without significant additional investments.

The UPS is designed with user-friendly management and monitoring capabilities. It includes an LCD panel that provides real-time information on system status, input/output voltages, battery condition, and more, allowing users to monitor performance effortlessly. Furthermore, it supports remote management via SNMP, allowing IT administrators to access and manage the system through a network interface, enabling proactive troubleshooting and maintenance.

In terms of battery management, the SU20K3/3XR5 comes with hot-swappable batteries. This feature allows for battery replacement without shutting down the UPS or connected equipment, enhancing uptime during maintenance procedures. Additionally, the system supports intelligent temperature compensation, which extends battery lifespan by adjusting charge voltage based on the operating temperature.

With its combination of advanced features, robust technology, and user-friendly design, the Tripp Lite SU20K3/3XR5 stands out in the market of uninterruptible power supplies. Businesses seeking reliability, scalability, and excellent energy efficiency will find this UPS to be an invaluable asset for protecting critical loads from power fluctuations and outages.