Tripp Lite SU6000RT4U Overload Messages, Bypass Messages, Overload Condition, Countdown Duration

Models: SU5000RT4U SU6000RT4U SU8000RT4U

1 48
Download 48 pages 31.93 Kb
Page 13
Image 13
Overload Messages

Operation (continued)

Overload Messages

When the UPS detects an output overload, its LCD will switch to the following display:

OVERLOAD!

LOAD1 = XXX% X.XKW

OVERLOAD!

LOAD2 = XXX% X.XKW

The UPS will then begin a countdown. If the UPS is still overloaded at the end of the countdown, the UPS will automatically go to BYPASS MODE to protect its inverter. The duration of the countdown varies with the severity of the overload, as follows:

Overload Condition

Countdown Duration

102% - 125%

1 minute

 

 

125% - 150%

30 seconds

 

 

> 150%

Immediate Bypass

 

 

Bypass Messages

While in BYPASS MODE, the UPS monitors its input voltage and passes that input power along to connected equipment. The UPS will not provide battery backup in BYPASS MODE. If the output voltage deviates from an acceptable range (between 15% higher and 20% lower than nominal), the UPS displays the condition on its LCD and stops supplying output power to its load. If power levels return to an acceptable level, the UPS resumes supplying power to the load, and its LCD reports that output voltage was too high or too low at one time, but has returned to nominal.

Bypass Voltage Conditions

LCD Screen Messages

L1 > 15% Higher

BYPASS AC1 HIGH

 

Than Nominal Voltage

LOAD1 = XXX% X.XKW

 

 

 

 

 

 

 

 

 

L2 > 15% Higher

 

 

 

BYPASS AC2 HIGH

 

Than Nominal Voltage

 

LOAD1 = XXX% X.XKW

 

 

 

 

 

 

 

 

 

 

 

L1 > 20% Lower

 

 

 

BYPASS AC1

LOW

 

Than Nominal Voltage

 

LOAD1 = XXX% X.XKW

 

 

 

 

 

 

 

 

 

L2 > 20% Lower

 

 

 

BYPASS AC2 LOW

 

Than Nominal Voltage

LOAD1 = XXX% X.XKW

 

 

 

 

 

 

 

L1 Voltage Was Too High,

 

 

BYPASS AC1 WAS HI

 

Now Returned to Nominal Voltage

LOAD1 = XXX% X.XKW

 

 

 

 

 

 

 

L2 Voltage Was Too High,

 

 

 

BYPASS AC2 WAS HI

 

Now Returned to Nominal Voltage

LOAD1 = XXX% X.XKW

 

 

 

 

 

 

 

L1 Voltage Was Too Low,

 

 

 

BYPASS AC1 WAS LO

 

Now Returned to Nominal Voltage

LOAD1 = XXX% X.XKW

 

 

 

 

 

 

 

L2 Voltage Was Too Low,

 

 

 

BYPASS AC2 WAS LO

 

Now Returned to Nominal Voltage

LOAD1 = XXX% X.XKW

 

 

 

 

 