Troubleshooting
(continued)
Lights (On/Flashing) and Condition Solution
On:FAULT,BYPASS, LINE, 100%, 75% Check the UPS to be sure that there is
Condition:On Bypass due to High adequate space for air to circulate near
Internal Temperature the vents and that the fan is working
properly.Restart the UPS.
Flashing:LINE This indicates that utility power is too high
Condition:Input Abnormal or low for the UPS to operate in BYPASS
mode, so if an inverter failure occurs,
the UPS will deliver no output.
On:FAULT,100% Restart the UPS.If the problem persists,
Flashing:LINE, BYPASS contact Tripp Lite for repairs.
Condition:No Output due to High
Output Voltage and Abnormal Input
Flashing:LINE, BYPASS
Restart the UPS.If the problem persists,
On: FAULT, 7 5% contact Tripp Lite for repairs.
Condition:No Output due to Low
Output Voltage and Abnormal Input
Flashing:LINE, BYPASS Restart the UPS.If the problem persists,
On: FAULT, 5 0% contact Tripp Lite for repairs.
Condition:No Output due to High
Bus Voltage and Abnormal Input
Flashing:LINE, BYPASS Restart the UPS.If the problem persists,
On: FAULT, 2 5% contact Tripp Lite for repairs.
Condition:No Output due to Low
Bus Voltage and Abnormal Input
Flashing:LINE, BYPASS Check the UPS to be sure that there is
On:FAULT,100%, 75% adequate space for air to circulate near
Condition:No Output due to High the vents and that the fan is working
Internal Temperature and Abnormal properly.Restart the UPS. If the problem
Input persists, contact Tripp Lite for repairs.