Battery Replacement (continued)
When replacing the batteries on a SU1500RTXL2U, SU1500RTXL2UHV, SUINT1500RTXL2U, SU2200RTXL2U, SU2200RTXL2UHV, SUINT2200RTXL2U, SU3000RTXL2U, SU3000RTXL2UHV or SUINT3000RTXL2U, qualified service personnel should refer to “Battery Warnings” in the Safety section and follow this procedure:
1)Place the UPS horizontal with its control panel on the right side.
2)Remove the left
3)Unscrew and remove the battery connector cover (B).
4)Disconnect battery connectors (C). Note: while batteries are disconnected, the UPS will not provide battery backup in the event of a power outage.
5)Unscrew and remove the battery cover plate (D).
6)Unscrew and remove the battery retaining bracket (E).
7)Grasp
8)Make a detailed sketch of the batteries and the polarity, color and connection of all cables. Disconnect used batteries and dispose of them properly. Connect replacement batteries in exactly the way the original batteries were connected. Note: Small sparks arcing between battery connectors during battery replacement are normal. Reassemble the UPS by reversing steps