Unified Brands VENTILATION SYSTEMS Calculating And Recording Air Movement, Exhaust, Supply

Models: VENTILATION SYSTEMS

1 33
Download 33 pages 54.59 Kb
Page 32
Image 32
CALCULATING AND RECORDING AIR MOVEMENT

CALCULATING AND RECORDING AIR MOVEMENT

1.) Cubic feet per minute or CFM'S is the total area multiplied by the average feet per minute.

A:

CFM

 

AREA

 

FPM

B:CFM = AREA x AVG. FPM FPM = CFM ⎟ AREA AREA = CFM ⎟ FPM

2.) AREA is the length of the opening multiplied by the width in inches. Divide the total by 144 to get the total square feet (area).

EXHAUST

A:Filter Hoods - Area = *Square Feet x Quantity of Filters

*16 x 20 Filter = 1.75 Square Feet

*20 x 20 Filter = 2.25 Square Feet

B:Extractor Type Hoods - Area = **Square Feet x Quantity of Modules

16” Standard Module

**Low Volume Extractor w/3" Slot = .32352 Square Feet **High Volume Extractor w/4" Slot = .43136 Square Feet

9” Standard Module

**Low Volume Extractor w/3" Slot = .1855 Square Feet **High Volume Extractor w/4" Slot = .2473 Square Feet

C:Water Wash Hood - Area = Length of Slot x Width of Slot in inches and divided by 144 for square feet.

SUPPLY

A:Perforated Supply Air Panels - Square Feet of Panel x .4 = Area.

B:Register Type Supply Air Panels - Square Feet of Panel x .7 = Area.

29

Page 32
Image 32
Unified Brands VENTILATION SYSTEMS specifications Calculating And Recording Air Movement, Exhaust, Supply