CIRCUIT BOARD FUNCTIONS

START-UP SEQUENCE OF EVENTS

Once the control panel is turned to on, a timer begins that will start, stop and continue operation of the American

Harvest as a preset temperature is achieved.

COMPONENT

OPERATION START

OPERATION END

Draft Fan

Starts Immediately

Will continue until shutdown. Shutdown will

 

 

occur when the operating temperature is

 

 

below 90 degrees.

Agitator

Three minutes after starting the agitator will

Will continue intermediately, as determined by

 

begin to turn

the “HEAT SETTING”, until shutdown

 

 

 

Auger

Three minutes after starting the auger will

The auger will continue at the feed rate

 

begin to turn

specified by the “HEAT SETTING”.

 

 

NOTE: Safety switches, HI limit and vacuum

 

 

sensor, must be activated to continue proper

 

 

operation.

 

 

 

Room Fan

Begins when 110 degrees is reached.

Will continue to operate until the heater cools

 

 

down to below 90 degrees. This may take

 

 

several minutes up to an hour.

Automatic Shutdown

If after 15 minutes, the heater has not reached

Should the timer expire before the preset

 

the preset operating temperature, the unit will

operating temperature is achieved, simply

 

begin to automatically shut down.

reset the stove by pressing the “ON” buttton.

Normal Operation

If after 15 minutes the preset operating tem-

Operation will continue until either the

 

perature of 110 degrees is achieved, normal

heater’s control is to the “OFF” position, or

 

operation will continue.

the operating temperature falls below 90

 

 

degrees. At such time the heater will default

 

 

to the “Automatic Shut Down”.

 

 

 

SHUTDOWN SEQUENCE OF EVENTS

Once the Heater has reached the normal operating temperature and switched to the “OFF” position, the unit will continue to operate on a much lower setting for 10 minutes. (Approximately half of the “1” setting). After 10 minutes the auger will slow down further and continue at this feed rate until the heater’s “LOW LIMIT SAFTEY” sensor tells the control board it is safe to shutdown.

COMPONENT

SHUTDOWN

OPERATION END

Draft Fan

Unchanged operation until preset “OFF” tem-

Continues until the operating temperature falls

 

perature is achieved.

below 90 degrees. May take several minutes

 

 

up to an hour.

 

 

 

Agitator

Continues at a lower sequence

Continues until the operating temperature falls

 

 

below 90 degrees.

Auger

Slows down to a “HALF SETTING” for 10

The auger will continue at the lower feed

 

minutes and then to a “QUARTER SETTING”

rates until the operating temperature falls

 

for the duration of the shutdown.

below 90 degrees.

 

 

NOTE: Safety switches, HI limit and vacuum

 

 

sensor, must be activated to continue

 

 

proper operation.

Room Fan

Unchanged operation until preset “OFF” tem-

Will continue to operate until the heater cools

 

perature is achieved.

down to below 90 degrees. This may take

 

 

several minutes up to an hour.

Automatic Shutdown

If the heater’s “HI LIMIT” sensor snaps open,

It is rare that the HI LIMIT temperature is

 

this will cause an automatic shutdown. An

reached. However, should this error occur,

 

error code will be displayed (Err1). NOTE: “HI

let the heater cool down for an hour then

 

LIMIT” errors are usually the result of operat-

restart.

 

ing at the highest heat setting for long peri-

 

 

ods of time, room fan failure or loose wire

 

 

connection.

 

 

 

 

22

 

USSC

Page 22
Image 22
United States Stove 6039I owner manual Circuit Board Functions, START-UP Sequence of Events