PART A, FIGURE 8

(FIGURE 8 CONTINUED ON NEXT PAGE)

MINIMUM 12 IN.

TO COMBUSTIBLES

CHIMNEY FLUE

MASONRY CHIMNEY CONSTRUCTED TO NFPA 211

MINIMUM CHIMNEY CLEARANCE TO BRICK AND COMBUSTIBLES IS 2 IN.

MINIMUM CLEARANCES 12 IN. OF BRICK ALL AROUND

CHIMNEY CONNECTOR TO HEATER

FIRE CLAY LINER

(5/8" MIN. WALL THICKNESS)

MIN. 3-1/2" THICK BRICK

MASONRY WALL

1.Use a minimum 3-1/2" thick brick masonry wall framed into the combustible wall. A fireclay liner (ASTM C315 or equivalent) having a 5/8" minimum wall thickness must be used and it must be at least 12" away from any material that could catch fire. The inside diameter of the fireclay liner shall be sized for the proper snug fit of a 6" diameter chimney connector pipe. The fireclay liner shall run from the outer surface of the brick wall to, but not beyond, the inner surface of the chimney flue and shall be firmly cemented in place. See Part A of Figure 8.

2.Use a solid insulated listed factory-built chimney length having an inside diameter of 6" and having 1" or more of solid insulation. There must be at least a 9" air space between the outer wall of the chimney length and any combustible materials. The inner end of the chimney length shall be flush with the inside of the masonry chimney flue shall be sealed to the flue and to the brick masonry penetration with nonwater-soluble refractory cement. Sheet steel supports which are at least 24 gauge (0.024") in thickness shall be securely fastened to wall

surfaces on all sides. Fasteners between supports and the chimney length shall not penetrate the chimney liner. See Part B of Figure 8.

3.Use a 10" diameter ventilated thimble made of at least 24 gauge (0.024") steel having two 1" air channels. The venti- lated thimble must be separated from combustible materials by a minimum of 6" glass fiber insulation. The opening in the combustible wall shall be covered and the thimble supported with sheet steel supports which are at least 24 gauge (0.024") in thickness. The sheet steel supports shall be securely fastened to wall surfaces on all sides and shall be sized to fit and hold the chimney section. Fasteners used to secure chimney sections shall not penetrate chimney flue liner. See Part C of Figure 8.

4.Use an 8" inside diameter solid insulated listed factory-built chimney length which has 1" or more of solid insulation. The minimum length of this chimney section shall be 12" and will serve as a pass-through for the 6" diameter chimney connector. There must be at least a 12" air space between the outer wall of the chimney section and any combustible materials. The chimney section shall be concentric with and spaced 1" away from the chimney connec tor by means of sheet steel support plates on both ends of the chimney section. The opening in the combustible wall shall be covered and the chimney section supported on both sides with sheet steel supports which are at least 24 gauge (0.024") in thickness. The sheet steel supports shall be securely fastened to wall surfaces on all sides and shall be sized to fit and hold the chimney section. Fasteners used to secure chimney sections shall not penetrate chimney flue liner. See Part C of Figure 8.

5.A listed factory-built wall pass-through system may be purchased and installed according to the instructions pack aged with it to provide a safe method of passing the chimney connector through a combustible wall for connection to a masonry chimney.

Additional requirements pertaining to Figure 8 and the above wall pass-through systems:

1.Insulation material used as part of wall pass-through system shall be of noncombustible material and shall have a thermal conductivity of 1.0 Btu • in./ft.² • °F (4.88 kg • cal/hr • m² • °C) or less

2.All clearances and thicknesses are minimums: larger clearances and thickness are acceptable.

3.A chimney thimble, as shown for 3" and 4" above (Parts C and D respectively of Figure 8) shall be for types "3" and 4" connections to facilitate removal of the chimney connector for cleaning. The chimney thimble shall be of ASTM C315 fireclay with 5/8" minimum wall thickness , or material or equivalent durability. The inside diameter of the

thimble shall be sized for the proper snug fit of a 6" diameter chimney connector pipe. The thimble shall be installed without damage to the chimney flue. The thimble shall extend through the chimney wall to, but not beyond, the inner surface of the chimney flue and shall be permanently cemented in place with high temperature cement.

4.A chimney connector to a masonry chimney, except for 2" above (Part B of Figure 8), shall extend through the wall pass-through system to the inner face of the chimney flue, but not beyond. It does not have to be fastened in place so long as it cannot accidently be pulled out of the chimney or shoved into the chimney flue. If fasteners are used to secure the chimney connector to a masonry chimney, the fasteners shall not penetrate the chimney flue liner.

5.Any material used to close up any opening for the connector shall be noncombustible.

7

Page 7
Image 7
United States Stove C226 owner manual On Next

C226 specifications

The United States Stove C226 is a striking combination of efficiency, performance, and style, making it an ideal choice for homeowners who seek reliable heating solutions. This wood and coal burning stove is engineered to provide substantial warmth while emphasizing ease of use and durability.

One of the main features of the C226 is its robust construction. Manufactured from heavy-duty cast iron and steel, this stove boasts exceptional durability and heat retention, ensuring that it can withstand even the most intense usage. The C226 is designed to handle a wide variety of wood sizes, accommodating logs up to 18 inches, and it is perfect for both rural and urban settings alike.

The C226 incorporates an ingenious technology known as "air wash" that helps keep the glass door clean for optimal viewing of the flickering flames. This feature reduces the buildup of creosote and soot, enhancing not only the aesthetic appeal but also the safety and efficiency of the stove.

Moreover, the stove's efficient combustion technology is designed to maximize heat output while minimizing emissions. This results in a cleaner burn, which is crucial for maintaining indoor air quality and for adhering to environmental regulations. The C226 also employs an easy-to-use damper that allows for precise control of the air supply, giving users the ability to fine-tune the burn rate according to their heating needs.

The design of the C226 includes a sizable firebox, which contributes to its long burn time. With a heat output rating capable of warming areas of up to 1,500 square feet, it is perfect for medium-sized homes and spaces. The stylish appearance, with its classic black finish and contoured edges, means it fits seamlessly into various interior decors.

Additionally, the C226 features a variety of installation options, compatible with both chimney and venting systems. The versatility of this stove makes it a popular choice among those looking to enhance their home’s heating capabilities while also enjoying the ambiance of a natural fire.

Overall, the United States Stove C226 stands out as a reliable and efficient heating solution. With its solid construction, user-friendly features, and environmentally-friendly performance, it exemplifies what a high-quality wood and coal stove should offer for today’s energy-conscious homeowners.