TROUBLESHOOTING

20

TROUBLESHOOTING

TROUBLESHOOTING

Note: For additional help, visit DESA International’s technical service web site at www.desatech.com.

Note: All troubleshooting items are listed in order of operation.

OBSERVED PROBLEM WARNING: Turn off fireplace and let cool before servicing. Only a qualified service person should service and repair fireplace.

POSSIBLE CAUSE CAUTION: Never use a wire, needle, or similar object to clean ODS/pilot. This can damage ODS/ pilot unit.

OBSERVED PROBLEM

POSSIBLE CAUSE

REMEDY

When ignitor button is pressed, there is no

1.

Ignitor electrode not connected to igni-

1.

Reconnect ignitor cable

spark at ODS/pilot

 

tor cable

 

 

 

2.

Piezo ignitor nut is loose

2.

Tighten nut holding piezo ignitor to base

 

 

 

 

panel of log set. Nut is located behind

 

 

 

 

base panel

 

3.

Ignitor cable pinched or wet

3.

Free ignitor cable if pinched by any

 

 

 

 

metal or tubing. Keep ignitor cable dry

 

4.

Broken ignitor cable

4.

Replace ignitor cable

 

5.

Bad piezo ignitor

5.

Replace piezo ignitor

 

6.

Ignitor electrode broken

6.

Replace pilot assembly

 

7.

Ignitor electrode positioned wrong

7.

Replace pilot assembly

 

 

 

 

 

When ignitor button is pressed, there is

1.

Gas supply turned off or equipment

1.

Turn on gas supply or open equipment

spark at ODS/pilot but no ignition

 

shutoff valve closed

 

shutoff valve

 

2.

Control knob not in PILOT position

2.

Turn control knob to PILOT position

 

3.

Control knob not pressed in while in

3.

Press in control knob while in PILOT

 

 

PILOT position

 

position

 

4.

Air in gas lines when installed

4.

Continue holding down control knob.

 

 

 

 

Repeat igniting operation until air is

 

 

 

 

removed

 

5.

ODS/pilot is clogged

5.

Clean ODS/pilot (see Cleaning and

 

 

 

 

Maintenance, page 19) or replace ODS/

 

 

 

 

pilot assembly

 

6.

Gas regulator setting is not correct

6.

Replace gas regulator

 

 

 

 

 

ODS/pilot lights but flame goes out when

1.

Control knob not fully pressed in

1.

Press in control knob fully

control knob is released

2.

Control knob not pressed in long enough

2.

After ODS/pilot lights, keep control

 

 

 

 

knob pressed in 30 seconds

 

3.

Equipment shutoff valve not fully open

3.

Fully open equipment shutoff valve

 

4.

Thermocouple connection loose at con-

4.

Hand tighten until snug, then tighten 1/4

 

 

trol valve

 

turn more

 

5.

Pilot flame not touching thermocouple,

5.

A) Contact local propane/LP gas company

 

 

which allows thermocouple to cool,

 

 

 

 

causing pilot flame to go out. This prob-

 

 

 

 

lem could be caused by one or both of

 

B) Clean ODS/pilot (see Cleaning and

 

 

the following:

 

Maintenance, page 19) or replace ODS/

 

 

A) Low gas pressure

 

pilot assembly

 

 

B) Dirty or partially clogged ODS/pilot

 

 

 

6.

Thermocouple damaged

6.

Replace pilot assembly

 

7.

Control valve damaged

7.

Replace control valve

 

8.

On thermostat models, safety interlock

8.

Wait one minute for safety interlock sys-

 

 

system has been triggered

 

tem to reset. Repeat ignition operation

For

 

.

 

.com

107156-01E

Page 20
Image 20
Vanguard Heating 107156-01E.pdf installation manual Troubleshooting, Observed Problem, Possible Cause, Remedy