FIREPLACE INSTALLATION
Continued
Test Pressures Equal To or Less Than 1/2 PSIG (3.5 kPa)
1. | Close manual shutoff valve (see |
| Figure 28). |
2. | Pressurize supply piping system by ei- |
Open
Manual
Shutoff
Valve
Closed
Figure 28 - Manual Shutoff Valve
ther opening propane/LP supply tank |
valve for propane/LP gas fireplace or |
opening main gas valve located on or near |
gas meter for natural gas fireplace, or |
using compressed air. |
3. Check all joints from propane/LP sup- |
ply tank or gas meter to manual shutoff |
valve (see Figure 29 for propane/LP or |
Figure 30 for natural). Apply commer- |
cial leak test solution to all gas joints. |
Bubbles forming show a leak. Correct |
all leaks at once. |
Pressure Testing Fireplace Gas Connections
1. Open manual shutoff valve (see |
Gas Valve |
Manual | Propane/ | |
LP Supply | ||
Shutoff | ||
Tank | ||
Valve | ||
|
| Figure 28). |
2. | Open propane/LP supply tank valve for |
| propane/LP fireplace or main gas valve |
| located on or near gas meter for natu- |
| ral gas fireplace. |
3. | Make sure control knob of fireplace is |
| in the OFF position. |
4. | Check all joints from manual shutoff |
| valve to thermostat gas valve (see Fig- |
| ure 29 for propane/LP or Figure 30 for |
| natural). Apply commercial leak test so- |
| lution to all gas joints. Bubbles forming |
| show a leak. Correct all leaks at once. |
5. | Light fireplace (see Lighting Instruc- |
| tions, page 18). Check all other inter- |
| nal joints for leaks. |
6. | Turn off fireplace (see To Turn Off Gas |
| to Appliance, page 18). |
Figure 29 - Checking Gas Joints for Propane/LP Gas Freestanding Fireplace
Manual |
Shutoff |
Valve |
Gas Meter |
Gas Valve |
Figure 30 - Checking Gas Joints for Natural Gas Freestanding Fireplace
14 | 105500 |