14
104059
COMPACT CLASSIC HEARTH FIREPLACE
VMH26TPA
®
CONNECTING TO GASSUPPLY
WARNING: A qualified ser-
vice person must connect fire-
place to gas supply. Follow all
local codes.
CAUTION: Never connect fire-
place directly to the propane/LP
supply. This fireplace requires
an external regulator (not sup-
plied). Install the external regula-
tor between the fireplace and pro-
pane/LP supply.
CAUTION: Use only new,
black iron or steel pipe. Inter-
nally-tinned copper tubing may
be used in certain areas. Check
your local codes. Use pipe of 1/2"
or greater diameter to allow
proper gas volume to fireplace. If
pipe is too small, undue loss of
pressure will occur.
CAUTION: Use pipe joint seal-
ant that is resistant to liquid pe-
troleum (LP) gas.
The installer must supply an external regu-
lator. The external regulator will reduce
incoming gas pressure. You must reduce
incoming gas pressure to between 11 and
14 inches of water. If you do not reduce
incoming gas pressure, fireplace regulator
damage could occur. Install external regu-
lator with the vent pointing down as shown
in Figure 22. Pointing the vent down pro-
tects it from freezing rain or sleet.
We recommend that you install a sediment
trap in supply line as shown in Figure 23.
Locate sediment trap where it is within
reach for cleaning. Install in piping system
between fuel supply and heater. Locate sedi-
ment trap where trapped matter is not likely
to freeze. A sediment trap traps moisture
and contaminants. This keeps them from
going into fireplace controls. If sediment
trap is not installed or is installed wrong,
fireplace may not run properly.
Propane/LP
Supply Tank
External Regulator

Attaching Wood Base to Solid

Floor

For attaching base to solid floors (concrete
or masonry)
Note:
Floor anchors and mounting screws
are in hardware package. The hardware pack-
age is provided with fireplace.
1. Drill holes at marked locations using
5/16" drill bit. For solid floors (concrete
or masonry), drill at least 1" deep.
2. Fold floor anchor as shown in Figure 21.
3. Insert floor anchor (wings first) into
hole. Tap anchor flush to floor.
4. Insert mounting screws through base
and into floor anchors.
5. Tighten screws until base is firmly fas-
tened to floor.
Figure 21 - Folding Anchor
Installation must include a manual shutoff
valve, union, and plugged 1/8" NPT tap.
Locate NPT tap within reach for test gauge
hook up. NPT tap must be upstream from
fireplace (see Figure 23).
IMPORTANT:
Install main gas valve
(manual shutoff valve) in an accessible
location. The main gas valve is for turning
on or shutting off the gas to the appliance.
Apply pipe joint sealant lightly to male
threads. This will prevent excess sealant
from going into pipe. Excess sealant in pipe
could result in clogged fireplace valves.
* Purchase the optional A.G.A. design-certified manual shutoff valve from your dealer.
See Accessories, page 27.
A.G.A. Design-Certified Manual
Shutoff Valve With 1/8" NPT Tap*
3" Minimum
From
External
Regulator
(11" W.C.
to 14" W.C.
Pressure)
Approved Flexible
Gas Line
Pipe Nipple Cap Tee Joint
Sediment Trap
Figure 23 - Gas Connection
Figure 22 - External Regulator with Vent
Pointing Down
Vent Pointing Down
INSTALLATION
Continued