Powerware 9315 operation manual Connecting Equipment to a Serial Port, Port 1 DE-9

Models: 9315

1 92
Download 92 pages 47.45 Kb
Page 49
Image 49

Connecting Equipment to a Serial Port

You can connect a wide variety of terminals, printers, and computers to each port, and configure the UPS as the Data Communication Equipment (DCE). Set up the remote equipment using the appropriate parameters for the mode you select. The following section provides more information about configuration.

The cables you use for connection depend on the equipment you are connecting to the UPS. Cables should be no longer than 16m (50 ft). The connectors for Port 1 and Port 2 on the Communications Panel in the UPS are female, so the cables should be male. Figure 24 shows the pin assignments for Port 1, and Table 2 describes them. Figure 25 shows the pin assignments for Port 2, and Table 3 describes them.

PORT 1 (DE-9)

+24V

1

 

NOT USED

RS232 TXD

 

6

2

 

 

485 +

 

7

RS232 RXD

 

3

 

 

485 --

 

 

NOT USED

 

8

4

 

 

RETURN

 

 

RETURN

 

9

5

 

 

 

 

 

 

Figure 24. Port 1 Pin Assignments

Table 2. Pin Assignments for Port 1 (DE---9)

Pin #

Symbol

Description

Comments

 

 

 

 

1

+24V

+ 24 volts DC

 

 

 

 

 

2

TXD

Transmit Data

Input to UPS

 

 

 

 

3

RXD

Receive Data

Output from UPS

 

 

 

 

5

RTN

Return

 

 

 

 

 

7

485+

RS485 + Data

 

 

 

 

 

8

485---

RS485 --- Data

 

 

 

 

 

9

RTN

Return

 

 

 

 

 

Powerware 9315 (200 kVA ---300 kVA) Operation

41

164201036 Rev. D 041500

 

Page 49
Image 49
Powerware 9315 operation manual Connecting Equipment to a Serial Port, Port 1 DE-9