Environmental Specifications
Operating Temperature | 0 to 40˚C without derating. However, operating | |
| at or near 40˚C will adversely affect battery life | |
| (refer to your battery specifications for more | |
| information). The recommended operating | |
| temperature is 25˚C. | |
|
| |
Operating Altitude | Maximum 1500m (5000 ft) at 40_C without | |
| derating | |
|
| |
Storage Temperature | ||
| will cause rapid battery | |
|
| |
Relative Humidity (operating and | 95% maximum noncondensing | |
storage) |
| |
|
| |
Acoustical Noise | 65 dBA at a 1m distance | |
|
| |
EMI Supression | Meets FCC Regulation 47, Part 15, Subpart J, for | |
| class A devices | |
|
| |
Electrostatic Discharge (ESD) | Meets IEC | |
Immunity | to 25 kV without damage and with no disturbance | |
| or adverse effect to the critical load. | |
|
| |
System Efficiency at Full Unity | 400V, 600V Models: | |
Power Factor Load and Nominal | 91% | |
Input Voltage | 480V Models: | |
Note: The 208/600 systems use an | ||
92% | ||
input isolation transformer | ||
option that reduces system | . | |
efficiency. | ||
| ||
|
|
Battery Specifications
These specifications are for batteries supplied by the UPS manufacturer in
Battery Type | Sealed, |
| cells |
|
|
Nominal Battery String | 480 VDC (240 cells) for Powerware Plus 225, 300 |
Voltage | 420 VDC (210 cells) for Powerware Plus 200, 250 |
Float Charging | 2.25 VDC per cell |
| (540 VDC based on 240 cells) |
| (470 VDC based on 210 cells) |
|
|
Equalizing Charge | 2.40 VDC per cell, set to 2.25 VDC at factory |
|
|
Battery Charge Current | Limited to 25% of full, regardless of actual load on inverter |
Limit |
|
|
|
Powerware 9315 (200 kVA | 77 |