Powerware 9315 operation manual System Output, Nominal +/-- 5%

Models: 9315

1 92
Download 92 pages 47.45 Kb
Page 84
Image 84

System Output

Rectifier/Charger Capacity

125%

 

 

DC Filtering

Ripple voltage less than 0.5% peak to peak

 

 

UPS Output Capacity

100% rated current at 0.8 power factor

 

 

Output Voltage Regulation

1% (10% to 100% load)

 

 

Output Voltage Adjustment

208 VAC nominal, adjustable from 198 VAC

(Nominal +/-- 5%)

to 218 VAC (60 Hz only)

 

480 VAC nominal, adjustable from 456 VAC

 

to 504 VAC (60 Hz only)

 

600 VAC nominal, adjustable from 570 VAC

 

to 630 VAC (60 Hz only)

 

400 VAC nominal, adjustable from 380 VAC

 

to 420 VAC (50/60 Hz)

 

 

Output Voltage Harmonic Content

3% max THD, 2% max single (for linear load)

 

 

Output Voltage Balance

3% for 100% maximum load imbalance

 

 

Output Voltage Phase

3˚ for 100% maximum load imbalance

Displacement

 

 

 

Output Transients

5% for 100% load step or removal

 

 

Frequency Regulation

0.01 Hz free running

 

 

Synchronous to Bypass

Bypass within voltage limits of +5%, ---8% of

 

output setting; bypass within 0.5 Hz

 

 

Frequency Slew Rate

1 Hz per second maximum (adjustable)

 

 

Overload Capability

125% for 10 minutes

 

150% for 10 seconds

 

 

Maximum Output Capability

300% peak for 10 cycles without bypass

 

 

76

Powerware 9315 (200 kVA ---300 kVA) Operation

 

164201036 Rev. D 041500

Page 84