48 Powerware 9315 (200 kVA---300kVA) Opera tion
164201036 Rev.D 041500
Meters Printout (Ctrl + M)

This key sequence prints the current readings of the UPS system meters. The

Input area shows the phase-to-phase voltage, frequency, and phase current of the

incoming utility, followed by thek VA, kW,and power factor measurements. The

output area shows the same informationfor the power being output by the UPS.

TheBypassareashowsthephase-to-phasevoltageofthebypasssource. The

Battery area displays theD C voltage(V) and the DC current (I). Figure 28 shows

a sample Meters printout.

Input Output
Bypass Battery
VAB
480
VBC VCA
KW
379
KVA
399
IA IB IC
FREQ
60.0
PF
0.95
V
540
I
0
480
480 480
480480
VAB
480
VBC VCA
480 480
IA IB IC
361 361361
IN
0
VAB
480
VBC VCA
480 480
FREQ
60.0
KVA
300
KW
240
PF
0.80
Uninterruptible Power System
UPS System Normal
Alarm: None
Notice: None
03 JAN 1997 14:22:49

+

Figure 28. System Meters
System Information Printout (Ctrl + A)

This key sequence prints a listing of all available serial data. This printout contains

the information shown on the Event History Log and Meters screens of the UPS

(both Figures 27 and 28).