20 Powerware 9315 (200 kVA---300kVA) Opera tion
164201036 Rev.D 041500

Using the LCD Screen

The LCD screen at the top of the Monitor Panelprovides an operator interface with
the UPS. Figure 9 ident ifies the display fields discussed in the following sections.
Uninterruptible Power System
System Normal
Alarm: None
Notice: None
Meters
System
Load Amps
Events Statistics Graphics Setup
Input Output
Bypass Battery
VAB
480
VBC VCA
KW
379
KVA
399
IA IB IC
FREQ
60.0
PF
0.95
V
540
I
000
Meters
480
480 480
480480
VAB
480
VBC VCA
480 480
IA IB IC
361 361361
IN
000
VAB
480
VBC VCA
480 480
FREQ
60.0
KVA
300
KW
240
PF
0.80
Battery
04 MAY 1997 14:23:45
100%
Percent
AEDCBFG
Figure 9. Parts of the LCD Screen (Typicalfor Power ware 9315 300 480/480V Unit)
AThe UPS status area contains three lines that display the current state of the UPS. The first
line shows the present operational mode ofthe UPS. The second line shows the highest level
of the current active alarms, and the third line shows any noticesthe UPS has posted. (For
more information about alarms and notices, refer to Chapter 11, “Responding to System
Events.”)
BThe battery chargebox shows the percentage of battery capacity available.
CThe menu box shows the currently selected menu and lists the optionsavailable on that
menu. The tit le at the top of the menu box is also shown below on the menu b ar (E). Press
the and pushbuttons to scroll up and down throughthe options in the menu box.
DThe currently selecte d option is highlightedin the menu box. Press the and pushbuttons
to move the highlight up or down. The data in the informationarea (G) changes accordingly.
EThe menu bar lists the titles of the menus. The title of the menu currently displayed in the
menu box is highlighted. When you press the and pushbuttons to move the highlight
left or right, the data in the menu box and the information area change accordingly.
FThe timestamp shows the current date and time. This date and time are recorded in the Event
Log when a notice or alarm is activated.