Powerware 9315 operation manual Path of Current Through the UPS in Battery Mode

Models: 9315

1 92
Download 92 pages 47.45 Kb
Page 20
Image 20

Battery Mode

The UPS transfers to Battery mode automatically if a utility power outage occurs, or if the utility power does not conform to specified parameters. In Battery mode, the battery provides emergency DC power that the inverter converts to AC power.

When the UPS switches to Battery mode, the alarm indications depend on the cause and condition of the battery charge. The length of time the system can operate in Battery mode depends on loading and the battery supply capacity.

Figure 5 shows the path of electrical power through the UPS when operating in Battery mode.

BYPASS

Bypass

Input

Rectifier

Input

K4

RECTIFIERINVERTER

CB1

K3 Output

(closed)

TRANSFORMER

BATTERY

Path of electrical power

Figure 5. Path of Current Through the UPS in Battery Mode

When the discharging battery voltage reaches the lower limit of UPS operation capability, the critical load transfers to Bypass mode if it is available. If Bypass input is not available, a “Shutdown Imminent” warning occurs. The warning time before critical load loss occurs is approximately 2 minutes, depending on battery capacity and the amount of loading.

If incoming power returns to within specified parameters, the UPS automatically returns to Normal mode and alarm indications clear. However, the process of returning to Normal mode is not instantaneous. The rectifier gradually draws increasing power from the incoming utility until Normal mode is achieved.

12

Powerware 9315 (200 kVA ---300 kVA) Operation

 

164201036 Rev. D 041500

Page 20
Image 20
Powerware 9315 operation manual Path of Current Through the UPS in Battery Mode