Product Specifications
The UPS systems are housed in freestanding,
system may be upgraded in the field to larger models:
System | Models | Notes | |
Powerware 9315 200 | 200 kVA | 50 | Hz or 60 Hz (400V models only) |
Powerware 9315 225 | 225 kVA | 60 | Hz only |
Powerware 9315 250 | 200 kVA & 250 kVA | 50 | Hz or 60 Hz (400V models only) |
Powerware 9315 300 | 225 kVA & 300 kVA | 60 | Hz only |
The following sections detail the input, output, environmental, and battery specifications for the UPS.
System Input
Operating Input | 480 VAC for operation from 408 VAC to 528 VAC (60 Hz only) |
Voltage |
|
(Nominal | 400 VAC for operation from 340 VAC to 440 VAC (50/60 Hz only) |
| 600 VAC for operation from 510 VAC to 660 VAC (60 Hz only) |
|
|
Operating Input | 3 Hz of nominal (50 Hz or 60 Hz) |
Frequency Range |
|
|
|
Operating Input | Battery Charge: |
Current | 125% of full load for overload + battery charge |
| Actual load + 25% of full load for battery charge |
| Reduced for Generator: |
| Adjustable, set to 102% |
|
|
Input Current | 10% THD at full load (with input filter option installed) |
Harmonic Content |
|
|
|
Power | Adjustable |
|
|
Power Factor | Minimum 0.95 |
|
|
Line Surges | 6 kV OC, 3 kA SC per ANSI 62.41 and IEC |
|
|
Powerware 9315 (200 kVA | 75 |