Powerware 9315 (200 kVA---300kVA) Opera tion
164201036 Rev.D 041500
Data/Stop
The data size and stop bits of the equipment connected to this port. These
settings determine the number of bits transmitted per ASCII character. The data
size and stop bits you specify depend on the configuration of your equipment.
For Port 1, the data size must be set to 8, with 1 or 2 stop bits. Settings of 7 data
bits/1 stop bit and 7 data bits/2 stop bits are available for Port 2.
NOTE: When connecting a computer running a terminal emul ation program, you
should set yourequipment to NO PARITY.
Handshaking
This setting controls handshaking. You can select XON/XOFF or Disabled for this
setting.

Disabled (No Handshaking)

If handshaking is disabled, the UPS will transmit and receive data via the serial
port, ignoring all inputs from handshaking lines.

XON/XOFF

If handshaking is enabled, the UPS uses special characters (XONand XOFF) to
handshake with the host terminal. The XON character is defined to be ASCII value
11 hex, and the XOFF character is defined to be ASCII value 13 hex. Upon
reception of an XOFF command, the UPS halts transmission until an XON
command is received. In the same way, if the terminal receives an XOFF
command, the UPS expects the terminal to halt transmission until the UPS sends
an XON command.
Save
Set to YES to save any changes to configuration settings upon exit from the Setup
screen. Set to NO if yo udo no t want to save any changes.
Default Settings
The following are the default configuration settings for the serial communications
ports:
Port 1 Remote Monitor 300 baud 8/1 Handshaking Disabled
Port 2 Terminal 9600 baud 8/ 1 Handshak ing Disabled
Each communications port on the UPS operates in one of five modes which you
select when configuring the port using the Setup Port screen.