Configuring the Serial Ports

You must configure the port for communications using the LCD screen and pushbuttons on the UPS Monitor Panel.

Select Port 1 or Port 2 from the Setup menu to display one of the Setup Port screens. The screens for Port 1 and Port 2 are identical, and allow you to specify settings for the two serial communication ports. Figure 26 shows the Setup Serial Port 1 screen.

 

 

Uninterruptible Power System

 

 

UPS System Normal

 

 

 

03 JAN 1997

14:23:45

Alarm:

None

 

 

 

 

 

 

Notice: None

 

 

 

 

 

 

Battery

 

 

 

 

 

 

Percent

 

 

 

 

 

 

100%

 

Setup Serial Port 1

 

 

 

 

 

 

 

Mode

Rate

Data/Stop

Handshaking

Save

 

 

TERMINAL

9600

8

1

XON / XOFF

NO

Setup

 

 

 

 

 

 

Port 1

 

 

 

 

 

 

Port 2

 

 

 

 

 

 

Time

 

 

 

 

 

 

 

Meters

Events

Statistics Graphics

Setup

 

 

 

 

Figure 26. Setup Serial Port 1 Screen

A small return arrow () appears in the upper right corner of the Setup Port

screen. This arrow is a reminder that you can press the pushbutton on the Monitor Panel to toggle the pushbuttons between the menu box and the information area.

If the scroll bar is in the menu box, press the pushbutton to toggle to the information area. The first setting (Mode) is highlighted. Press the or pushbutton to move the highlight to the setting you want to change. To scroll through the available options for that setting, press the or pushbutton.

To save the settings upon exit from this screen, be sure the Save field is set to YES.