Relay Interface Module

An optional Relay Interface Module (RIM) uses relay contact closures to indicate the operating status and alarm condition of the UPS system. A maximum of two monitoring accessories (RMPs, RIMs, or SCMs) can be installed. See Table 1 for the number of accessories permitted. Figure 21 shows the RIM with its four 15-pin connectors labeled J1 through J4.

Figure 21. Relay Interface Module

The RIM can provide these signals:

·UPS AVAILABLE (pins 1 and 12) Contacts are closed when the UPS is offline.

·UPS OFF LINE (pins 3 and 13) Contacts are closed when the UPS is operating in Normal mode.

·UTILITY FAILURE (pins 6 and 15) Contacts are closed when Utility Failure is detected.

·BATTERY WEAK (pins 5 and 14) Contacts are closed when approximately 2 minutes of battery time is remaining, before the critical load is lost.

36

Powerware 9315 (200 kVA ---300 kVA) Operation

 

164201036 Rev. D 041500