Powerware 9315 operation manual Relay Interface Module

Models: 9315

1 92
Download 92 pages 47.45 Kb
Page 44
Image 44

Relay Interface Module

An optional Relay Interface Module (RIM) uses relay contact closures to indicate the operating status and alarm condition of the UPS system. A maximum of two monitoring accessories (RMPs, RIMs, or SCMs) can be installed. See Table 1 for the number of accessories permitted. Figure 21 shows the RIM with its four 15-pin connectors labeled J1 through J4.

Figure 21. Relay Interface Module

The RIM can provide these signals:

·UPS AVAILABLE (pins 1 and 12) Contacts are closed when the UPS is offline.

·UPS OFF LINE (pins 3 and 13) Contacts are closed when the UPS is operating in Normal mode.

·UTILITY FAILURE (pins 6 and 15) Contacts are closed when Utility Failure is detected.

·BATTERY WEAK (pins 5 and 14) Contacts are closed when approximately 2 minutes of battery time is remaining, before the critical load is lost.

36

Powerware 9315 (200 kVA ---300 kVA) Operation

 

164201036 Rev. D 041500

Page 44
Image 44
Powerware 9315 operation manual Relay Interface Module