Battery Test Setup
If Battery Test Setup is selected from the main menu, the following menu is displayed:
Battery Test Setup
1.Setup
2.Setup Monthly Battery Test
3.Setup Quarterly Battery Test
4.Cancel Pending Battery Test
5.Display Next Scheduled Battery Test
6.Return to Main Menu
Enter Selection:
This menu allows you to schedule, review schedule, or cancel pending battery tests. The following menu is displayed when
Enter Starting Month
Enter Day of Week, Sunday = 1,
Enter Hour of Test
Enter Minute of Test
NOTE: Follow each entry with <CR>.
<CR> with no entry will return to Battery Test Setup Menu.
Enter the information at the prompt with a carriage return to schedule the battery test.
If entry 4 is selected from the Battery Test Setup menu, you will be prompted to enter “Y” to cancel all pending tests. This selection will only cancel pending tests and will not stop a test currently in progress.
If entry 5 is selected from the Battery Test Setup menu, and if a Battery Test is scheduled, the following menu is displayed:
Next Battery Test Scheduled
WK DAY MON HR:MN 4 FRI MAR 15:34
NOTE: Enter <CR> to return to Battery Test Setup Menu.
If 5 is selected and there are no tests scheduled, the following will be displayed:
No Battery Test Scheduled
Enter <CR> to return to Battery Test Setup Menu
NOTE: The unit will only perform one battery test in any 24 hour period.