51
Powerware 9315 (200 kVA---300kVA) Opera tion
164201036 Rev.D 041500
Enable/Disable Default Functions
From this menu you may either enable the building alarms for general functions or
specialfunctionssuchasOnGenerator,GoToBypass,andGoToUPS. Youmay
also customize the alarm messages from this menu. When 1 is selected from this
menu, the following menu is displayed:
Enable/Disable Default Functions
1. Enable/Disable Go To Bypass
2. Enable/Disable Go To UPS
3. Enable/Disable On Generator
4. Enable/Disable BuildingAlarm
5. Return to Program BuildingAlarms Menu
Enter Selection:
If you select entry 1---3 from this menu, the following menu will be displayed:
Enable/Disable (Function)
Enabled Building Alarm Number(s)
14
Enter E# to Enable Building Alarm Number #
Enter D# to Disable Building Alarm Number #
Enter <CR> for No Change
Enter Selection:
Where (Function) indicates the function the building alarm is being programmed for.
The line following the Enabled Building Alarm Number(s) label indicates which
building alarms are currently enabledfo r the function. (In this example, Building
Alarms 1 and 4 are enabled.) A building alarm can only be programmed for one
special function at a time from these menus. Enabling a building alarm for a
special function automatically enables the alarm. If you disable a special function,
the building alarm is also disabled.
If you select entry 4 from this menu, the following menu will be displayed:
Enable/Disable Building Alarm
Enabled Building Alarm Number(s)
14
Enter E# to Enable Building Alarm Number #
Enter D# to Disable Building Alarm Number #
Enter <CR> for No Change
Enter Selection:
The line following the Enabled Building Alarm Number(s) label indicates which
building alarms are currently enabled. (In this example, Building Alarms 1 and 4
are enabled.)