Through the Fireplace
If your fireplace opening height is at least 737 mm (29"), you may install a Defiant through the opening using a “positive connection” kit, available from your local deal- er. Positive connection kits ensure a tight fit between the stove flue collar and the chimney flue. (Fig. 8)
Fireplace installations, whether connected to the flue above or through the fireplace opening, have special clearance requirements to adjacent trim and the mantel. You’ll find the required safe clearances for Defiant fire- place installations on Page 12.
Floor protection requirements also apply to fireplace installations.
Defiant 1610CE
Your local dealer or your local building inspector can provide details for other approved methods of passing a chimney connector through a combustible wall in your area.
DO NOT CONNECT THE DEFIANT TO ANY AIR DIS- TRIBUTION DUCT OR SYSTEM.
460 mm (18”) clear- ance between pipe and sides/top/bottom of opening
T
DEFIAN
Flexible
Connector
Mantel Shield
Fireplace Adapter Kit
“Positive Connection”
ST245
Fig. 8 Through the fireplace installation.
Wall Pass-Throughs
Whenever possible, design your installation so the con- nector does not pass through a combustible wall. If you are considering a wall
Also, check with the chimney connector manufacturer for any specific requirements.
Accessories are available for use as wall pass- throughs. If using one of these, make sure it has been tested and listed for use as a wall
Figure 9 shows one method of passing a connector through a wall. All combustible material in the wall is cut away to provide the required 457 mm (18”) clearance for the connector. The resulting space must remain empty. A
ST494
Fig. 9 An approved wall
Hearths
This appliance must be installed on to hearth that meets the requirements of Part J of the Building Regu- lations 2000 (Combustion Appliances and Fuel Storage Systems). This can be achieved by ensuring that the hearth is constructed and sized in accordance with the guidelines included in section 2 of approved document ‘J’. The size and clearances of the hearth are as fol- lows:
The constructed hearth should be constructed in ac- cordance with the recommendations in document J, and should be of minimum width 840 mm and minimum depth 840 mm (if a free standing hearth b) above) or a minimum projection of 150 mm from the jamb (if a recessed hearth a) above).