Vermont Castings DVR28 Direct Vent Gas Fireplace

White Green

Orange

Wireless Remote

 

 

 

 

ON

 

 

 

 

OFF

HI/LO DC

 

Pilot

Module

 

Motor Drive

 

HI

 

 

 

Main

AF-4000

 

LO

 

 

 

 

Red

 

 

 

No wiring required.

 

 

Orange

(Refer to Pages 6,19, 23)

Black

 

AF-4000B/P

 

Red

 

 

 

 

Brown

 

 

 

 

Black

 

Red

 

Black

Gnd

 

Black

 

 

 

Brown

 

 

 

HI/LO DC Battery Pack

(SWI)

 

 

 

Brown

 

 

 

(SWI)

 

 

 

 

Black

 

 

 

 

Optional DC

 

 

 

Red

FP1750

 

 

Battery Back-up

 

 

 

 

 

 

 

Fig. 8 DVR28 wiring diagram.

Restrictor Plate Installation

The DVR28IN is shipped with a restrictor plate for ex- tended pipe runs other than straight out installations. A guide for usage is shown in Figure 10.

NOTE: Some installations may require some adjust- ment by the installer for optimum flame appearance. Optimum flame appearance would be a flame not subject to tall dirty yellow flames or lifting of flames from burner tube.

Installation

1.Remove front glass assembly. Refer to Window Frame Removal section on Page 18.

2.Remove three (3) screws securing flue diverter to top of combustion case. Remove flue diverter. (Fig. 9) CAUTION: Use care not to damage rear refractory.

3.Remove two (2) screws on sides of flue opening.

4.Install restrictor plate with two (2) screws removed from back of unit. (Fig. 9)

5.Re-install flue diverter with three (3) screws removed earlier.

6.Reinstall glass assembly. (Refer to Page 18)

Flue Diverter

 

Remove

 

Three (3)

FP1789

Screws

Flue

Restrictor

Opening

Remove

Plate

 

Two (2)

 

Screws

 

FP1788

FP1790

Fig. 9 Install restrictor plate for optimum flame appearance.

Examples for Extended Run/Restrictor Plate Settings

1.90° Elbow, vertical 8’ (2.4 m), 90° elbow, out 20’ (6 m)

2.90° Elbow, vertical 11’ (3.4 m), 90° elbow, out 13’ (4 m)

3.90° Elbow, vertical 20’ (6 m), 90° elbow, out 7’ (2 m)

4.90°, 40’ (12 m) vertical

Flue restricted to:

1.1¹⁄” (29 mm) opening in flue pipe outlet

2.7/8” (22 mm) opening in flue pipe outlet

3.3/4” (79 mm) opening in flue pipe outlet

4.1³⁄” (35 mm) opening in flue pipe outlet

Figure 10

20012301

7

Page 7
Image 7
Vermont Casting DVR28IN installation instructions Restrictor Plate Installation