Vermont Casting SC36, SR42, SR36, SC42 Side Wall Protection, Examples of wall shield insulation

Models: SR36 SR42 SC42 SC36

1 24
Download 24 pages 3.55 Kb
Page 15
Image 15
Side Wall Protection

Side Wall Protection

Adjacent combustible side walls that are within the minimum dimensions shown in Figure 23 of fireplace opening must be protected with Vermont Castings, Majestic Products Wall Shield Model SP40 or a specifically built wall shield described below.

The special wall shield design described in Figure 20 is an alternate method of adding protection to side

Majestic Fireplaces® SR/SC Series

MANTEL SHELF Examples of wall shield insulation:

FINISHED

WALL

See mantel drawing for

 

STUD

shelf-to-surround dimension

 

 

 

 

2 x 4 FINISHED

Must be sealed with

HEADER

 

noncombustible material

STANDOFF

walls and can be used in place of the SP40 with the same wall clearances specified for the SP40. Rt must =1.85 minimum.

Examples of wall shield insulation:

1.Manville - CERAFORM 126, K=.27, 1/2 inches thick

2.Majestic - EH2416, K = .458, 1 inch thick required.

TOP

VIEW

FIREPLACE FRONT

SURROUND Manual background

FIREPLACE

FRONT SIDE

VIEW

Manual background ¹⁄₂"

2 x 4 STUD Manual background FINISHED WALL

Manual background Must be sealed with noncombustible material

Fig. 21 Fireplace surround flush with finished wall.

12"

1¹⁄₂" Manual backgroundRef.

Combustible materials are permitted within a shaded area shown in Figure 23, page 16 titled Minimum Wall Clearances.

MA81

Fig. 22 Combustible mantle clearances.

15

Page 15
Image 15
Vermont Casting SC36, SR42, SR36 Side Wall Protection, Examples of wall shield insulation, Majestic Fireplaces SR/SC Series