Majestic Fireplaces® SR/SC Series
■9. Hearth Installation
A hearth extension is required to protect a combustible floor in front of the fireplace. Refer to Figure 23 for minimum dimensions and mounting detail.
Note: Hearth Extension must not cover the air inlet opening of a fireplace.
The hearth extension described in Figure 23 must be a durable
The top of insulation must be covered with a non- combustible decorative covering or a piece of .018” minimum sheet metal, to protect hearth extension material. (Fig. 23)
Secure the hearth extension to the floor to prevent shifting, using trim molding or other similar means at three (3) outer edges. Seal crack between the fire- place hearth and hearth extension with a
WARNING: HEARTH EXTENSION MUST BE INSTALLED IN ACCORDANCE WITH FIGURE 23 AND MUST NOT COVER THE BOTTOM FRONT OPENING OF THE CIRCULATING MODEL.
Alternate noncombustible materials may be used providing the (total) thermal resistance (Rt value) of the alternate material employed is greater than or equal to R = 1.09. Thermal resistance (R) or thermal conductivity (K), may be obtained from manufacturer of the material. Factors are related by the formula K = 1/R.
T = given thickness
R = thermal resistance for a given thickness (T) K = thermal conductivity
Noncombustible material with a lower R value may be used, provided thickness of material is sufficiently greater to maintain an equivalent (total) thermal resistance (Rt).
Minimum Wall Clearances
WITH | WITHOUT |
Noncombustible | Noncombustible |
Surround Facing | Surround Facing |
Shaded area starts
1/2" away from
4" BRICKedge of unit. (Example material)
|
|
| 4" |
|
E | F** | FIREBOX | E | D |
| OPENING |
| ||
|
|
|
| |
C** |
| A - Min. clearance |
|
|
|
| to combustible |
|
|
|
| perpendicular wall |
|
|
SIDE |
| B - Min. clearance | SIDE | |
WALL |
| to combustible | WALL | |
|
| perpendicular wall when |
|
|
|
| using noncombustible wall shield* |
|
|
Combustible material permitted within shaded area.
*Noncombustible wall shield requires 1" Majestic EH2416 insulation (minimum R Value = 1.85) between decorative noncombustible rigid covering and combustible wall.
Minimum height and width is 40" x 40".
**Dimension/degree of angle will vary depending on thickness of noncombustible surround facing.
Minimum Hearth Extension Dimensions
(for
| G | G |
| H |
|
|
| J |
| Seal cracks |
|
May install | between the |
|
noncombustible | fireplace |
|
decorative | and hearth |
|
covering | extension with |
|
OR .018" min. | noncombustible |
|
sheet metal | material | FIREPLACE |
|
| HEARTH |
4" MIN. |
|
|
COMBUSTIBLE | MINIMUM | Safety strips |
FLOOR | INSULATION | must overlap |
| VALUE "R" | ¹⁄₂" minimum |
|
| A | B | C | D | E | F | G | H | J |
|
| SR/SC36 | 16" | 12" | 48° | 41° | 18" | 14" | 7³⁄₄" | 16" | 48" |
|
|
| 406mm | 305mm |
|
| 457mm | 356mm | 197mm | 406mm | 1219mm |
|
| SR/SC42 | 20" | 12" | 42° | 35° | 18" | 14" | 11¹⁄₂" | 20" | 61¹⁄₂" |
|
|
| 508mm | 305mm |
|
| 457mm | 356mm | 292mm | 508mm | 1562mm | FP594 |
|
|
|
|
|
|
|
|
|
|
|
|
Fig. 23 Combustible side wall protection and hearth extension dimensions.
16