Vermont Castings VCBVTN/TP & VCPVTN/TP Room Heater
Pressure
Regulator
3/8” NPT Nipple
|
|
|
|
|
|
|
|
GaugeTest | Connection |
|
| Tee Joint | |||
| Reducer | ||||||
|
|
|
|
| Bushing to | ||
|
|
|
|
| 1/8” NPT | ||
|
|
|
|
| |||
|
|
|
|
| 1/8” NPT | ||
|
|
|
|
| Plug Tab | ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Sediment Trap |
|
|
|
| Tee Joint | ||
|
|
|
|
|
| Cap | |
|
|
|
| Pipe Nipple | |||
RH103 |
|
|
|
| |||
|
|
|
|
Fig. 6 Gas line connection.
Heater
Cabinet
Ground Joint
Union
Manual
Valve
From Gas
Meter
Natural Gas (4” w.c. to
10.5” w.c. Pressure) LP Gases
(11.5” w.c. to
14.0” w.c. Pressure)
Open
Closed
Manual
Valve
Control Valve
Manual |
Valve |
RH104
Fig. 7 Manual
Leak Testing Heater Gas Connections
Pressure Test Gas Supply Piping System
The appliance and its individual
The appliance must be isolated from the gas supply piping system by closing the individual manual
1.Open manual shut-off valve.
2.Open main gas valve located near gas meter.
3.Make sure control knob of heater is in the OFF position.
4.Check all joints from manual gas valve up to control valve and including the manifold assembly. Apply the soap solution around the connections, valve and tubing. Soap bubbles will appear where a leak is present.
5.If a leak is present, immediately turn off gas supply, tighten any leaky fittings, turn gas on and recheck.
6.To check burner and safety valve, the burner must be lit (see Operating Instructions). Check the rest of the connections for leaks.
7.Turn off the heater.