Vermont Casting VCBV30TN, VCPV10TN Leak Testing Heater Gas Connections, Open manual shut-offvalve

Models: VCBV30TN VCBV10TP - 10 VCBV20TN VCBV10TN VCBV20TP - 20 VCPV30TN VCPV10TN VCBV30TN, VCBV30TP, VCBV20TN, VCBV20TP, VCBV10TN, VCBV10TP, VCPV30TN, VCPV30YP, VCPV18TN, VCPV18TP, VCPV10TN, VCPV10TP VCPV18TP - 18 VCPV18TN VCPV10TP VCBV30TP - 30 VCPV30TP - 30

1 16
Download 16 pages 42.72 Kb
Page 7
Image 7
Open

Vermont Castings VCBVTN/TP & VCPVTN/TP Room Heater

Pressure

Regulator

3/8” NPT Nipple

 

 

 

 

 

 

 

 

GaugeTest

Connection

 

 

Tee Joint

 

Reducer

 

 

 

 

 

Bushing to

 

 

 

 

 

1/8” NPT

 

 

 

 

 

 

 

 

 

 

1/8” NPT

 

 

 

 

 

Plug Tab

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Sediment Trap

 

 

 

 

Tee Joint

 

 

 

 

 

 

Cap

 

 

 

 

Pipe Nipple

RH103

 

 

 

 

 

 

 

 

Fig. 6 Gas line connection.

Heater

Cabinet

Ground Joint

Union

Manual

Shutt-Off

Valve

Leak Testing Heater Gas Connections From Gas

Meter

Natural Gas (4” w.c. to

10.5” w.c. Pressure) LP Gases

(11.5” w.c. to

14.0” w.c. Pressure)

Open

Closed

Manual

Shut-Off

Valve

Control Valve

Manual

Shut-Off

Valve

RH104

Fig. 7 Manual shut-off valve location.

Leak Testing Heater Gas Connections

Pressure Test Gas Supply Piping System

The appliance and its individual shut-off valve must be disconnected from the gas supply piping system during any pressure testing of the system at test pressures in excess of 1/2 psi.

The appliance must be isolated from the gas supply piping system by closing the individual manual shut-off valve (Fig. 7) during any pressure testing of the gas supply system at test pressures equal to or less than 1/2 psi.

1.Open manual shut-off valve.

2.Open main gas valve located near gas meter.

3.Make sure control knob of heater is in the OFF position.

4.Check all joints from manual gas valve up to control valve and including the manifold assembly. Apply the soap solution around the connections, valve and tubing. Soap bubbles will appear where a leak is present.

5.If a leak is present, immediately turn off gas supply, tighten any leaky fittings, turn gas on and recheck.

6.To check burner and safety valve, the burner must be lit (see Operating Instructions). Check the rest of the connections for leaks.

7.Turn off the heater.

7

Page 7
Image 7
Vermont Casting VCBV30TN Leak Testing Heater Gas Connections, Pressure Test Gas Supply Piping System, Turn off the heater