VIKING RANGE, LLC | Downdraft Ventilators |
|
|
TAKE MEASUREMENTS (CONTINUED) |
|
Interior Blower Installation
Exterior Blower Installation
SIDE VIEW
OF DOWNDRAFT
WITH
VIDV500
INTERIOR
BLOWER
VIDV500 |
INTERIOR |
BLOWER |
SIDE VIEW
OF DOWNDRAFT
WITH
10" ROUND ELBOW
(for connection
to VEDV900 or VEDV1200
(DIPR150RSS only))
PLAN THE DUCTWORK
Interior Blower Installation
Exterior Blower Installation
1.The interior down- draft blower system is designed for use with
LEFT
DISCHARGE
1.The exterior downdraft blower system is designed for use with 10" round duct- work.
2.For best performance: Plan ducting which has the shortest length of ductwork and a minimum number of elbows. Check location of floor joists, wall studs, elec- trical wiring or plumbing for possible interference.
2. For best performance: |
| RIGHT | ||
Choose the ducting |
| DISCHARGE | ||
option which allows |
|
| ||
the shortest length | DOWN DISCHARGE | |||
of ductwork and a |
|
|
| |
minimum number of elbows and transitions. Check location | ||||
of floor joists, wall studs, electrical wiring or plumbing for | ||||
possible interference. |
|
| ||
|
|
|
| |
6" ROUND |
| |||
ELBOW |
| TRANSITION |
| 90O ELBOW |
EQUALS 6 FT. OF |
| EQUALS |
|
|
| 2 FT. OF |
| EQUALS 8 FT. OF | |
STRAIGHT DUCT |
| STRAIGHT DUCT |
| |
|
| STRAIGHT DUCT | ||
|
|
|
| |
|
|
|
|
|
3.The system will operate most efficiently when the ductwork does not exceed 40 feet of equivalent duct. The chart, above, shows equivalent feet of elbows and transitions. The number of feet of straight duct plus the equivalent feet of transitions and/or elbows to be used should equal 40 feet or less.
NOTE: The equivalent feet of various roof and wall caps has been taken into consideration. Do not include them in this
calculation.3
| 10" ROUND | |
| DISCHARGE | |
| PLATE | |
|
| |
10" ROUND | EQUALS 6 FT. OF |
|
ELBOW | STRAIGHT DUCT |
|
|
|
|
3.The system will operate most efficiently when the ductwork does not exceed 40 feet of equivalent duct. The illustration, above, shows equivalent feet of a 10" round elbow.The number of feet of straight duct plus the equivalent feet of elbows to be used should equal 40 feet or less.
NOTE: The equivalent feet of various roof and wall caps has been taken into consideration. Do not include them in this calculation.