Viking Sprinkler 11a Sprinkler Temperature, Sprinkler Nominal, Maximum Ambient, Bulb Color

Models: Sprinkler 11a

1 8
Download 8 pages 35.57 Kb
Page 3
Image 3
TABLE 1: AVAILABLE SPRINKLER TEMPERATURE RATINGS AND FINISHES

March 7, 2008

Sprinkler 11c

MICROMATIC® AND

TECHNICAL DATA MicromaticHP® STANDARD

RESPONSE PENDENT

SPRINKLERS

The Viking Corporation, 210 N Industrial Park Road, Hastings MI 49058

Telephone: 269-945-9501 Technical Services 877-384-5464 Fax: 269-945-4495 Email: techsvcs@vikingcorp.com

TABLE 1: AVAILABLE SPRINKLER TEMPERATURE RATINGS AND FINISHES

Sprinkler Temperature

Sprinkler Nominal

Maximum Ambient

Bulb Color

Classification

Temperature Rating1

Ceiling Temperature2

 

Ordinary

135 °F (57 °C)

100 °F (38 °C)

Orange

Ordinary

155 °F (68 °C)

100 °F (38 °C)

Red

 

 

 

 

Intermediate

175 °F (79 °C)

150 °F (65 °C)

Yellow

 

 

 

 

Intermediate

200 °F (93 °C)

150 °F (65 °C)

Green

 

 

 

 

Intermediate

212 °F (100 °C)

150 °F (65 °C)

Green

 

 

 

 

High

286 °F (141 °C)

225 °F (107 °C)

Blue

 

 

 

 

Extra High

360 °F (182 °C)

300 °F (149 °C)

Mauve

 

 

 

 

Ultra High3

500 °F (260 °C)

465 °F (240 °C)

Black

 

 

 

 

Sprinkler Finishes: Brass, Chrome-Enloy®, White Polyester, Black Polyester, and Black Teflon®

Corrosion-Resistant Coatings4: White Polyester, Black Polyester, and Black Teflon® in all temperature ratings. Wax-Coated Brass and Wax over Polyester5 for sprinklers with the following temperature ratings:

135

°F (57 °C) Off-White Wax

155 °F (68 °C) Lt. Brown Wax 175 °F (79 °C) Brown Wax 200 °F (93 °C) Brown Wax

212

°F (100 °C) Dk. Brown Wax6

286 °F (141 °C) Dk. Brown Wax6

Footnotes

1The sprinkler temperature rating is stamped on the deflector.

2Based on NFPA-13. Other limits may apply, depending on fire loading, sprinkler location, and other requirements of the Authority Having Jurisdiction. Refer to specific installation standards.

3Sprinklers of Ultra-High temperature rating are intended for use inside ovens, dryers, or similar enclosures with normal oper- ating temperatures above 300 °F (149 °C). Where the ambient temperature around the Ultra-High temperature rated sprinkler is significantly reduced below 300 °F (149 °C), response time may be severely retarded.

4The corrosion-resistant coatings have passed the standard corrosion test required by the approving agencies indicated on pages 11 d-e. These tests cannot and do not represent all possible corrosive environments. Prior to installation, verify through the end-user that the coatings are compatible with or suitable for the proposed environment. For automatic sprinklers, the coatings indicated are applied to the exposed exterior surfaces only. Note that the spring is exposed on sprinklers with Polyester and Teflon® coatings. For Teflon® coated open sprinklers only, the waterway is coated.

5Wax Over Polyester is unavailable for Sprinklers VK023 and VK122.

6Wax melting point is 170 °F (76 °C) for 212 °F (100 °C) and 286 °F (141 °C) temperature rated sprinklers.