DESIGN CRITERIA
(Also refer to the Approval Charts on pages
cULus Listing Requirements:
Micromatic® and MicromaticHP® Standard Pendent Sprinklers are cULus Listed as indicated in the Approval Charts for installation in accordance with the latest edition of NFPA 13 for standard spray sprinklers.
•Designed for use in Light, Ordinary, and Extra Hazard occupancies (exception: small orifice sprinklers are limited to Light Hazard where al- lowed by the installation standards being applied, with hydraulically calculated wet systems only).
•The sprinkler installation rules contained in NFPA 13 for standard spray pendent sprinklers must be followed.
FM Approval Requirements:
Standard Pendent Sprinklers are FM Approved as indicated in the Approval Charts for installation in accordance with the latest applicable FM Loss Prevention Data Sheets (including
NOTE: The FM installation guidelines may differ from cULus and/or NFPA criteria.
IMPORTANT: Always refer to Bulletin Form No. F_091699 - Care and Handling of Sprinklers. Also refer to page