Viking VCWB300 manual DIAGNOSTIC CHECK POINTS con’t

Models: VCWB300

1 24
Download 24 pages 31.13 Kb
Page 14
Image 14
DIAGNOSTIC CHECK POINTS (con’t)

DIAGNOSTIC CHECK POINTS (con’t)

E4 Thermister inputs (measured with thermisters disconnected).

1 to 8 3 to 4.5 VDC – TE2 (Evaporator Thermister #2)

2 to 9 3 to 4.5 VDC – TC1 (Compartment Thermister #1) 3 to 10 3 to 4.5 VDC – TE1 (Evaporator Thermister #1)

4 to 11 3 to 4.5 VDC – TC3 (Compartment Thermister #3) 5 to 12 3 to 4.5 VDC – TE3 (Evaporator Thermister #3)

6 to 13 3 to 4.5 VDC – TC2 (Compartment Thermister #2) 7 to 14 3 to 4.5 VDC

Compressor Relay

(use E3 – 16 as common for measurements)

Com

115

VAC continuous (power line supply).

NO

115

VAC when compressor is running.

NC

Not connected.

Alarm wires

(check for continuity – these are contact closures only)

Black

Common

Red

Normally closed (in no – alarm condition)

White

Normally open (in no – alarm condition)

Display Board (IDB5D –4330)

E1

Display Board receive

1+5VDC

2data signals

3ground

E2

Futaba VFD display data connection

TE = Thermister / Evaporator -- Cut-in (39°F minimum) for Evaporator Temperature TC = Thermister / Compartment – Compartment cut-out Temperature.

Thermister Tolerance ± 2 degrees.