| TROUBLESHOOTING GUIDE (con’t) | |
PROBLEM | POSSIBLE CAUSE | CORRECTION |
|
|
|
A. Warm temperature | b2 | Check for continuity across |
In all Wine Storage |
| the motor windings of the |
Compartments. |
| inoperative fan motor (See |
|
| pages 14 and 19). |
8. | Condenser Air / Flow |
|
|
| Condenser Fan Fault |
|
|
a. | Dirty condenser | a. | Clean condenser |
b. | Condenser fan blade | b. | Check fan blade. Tighten or |
| loose or obstructed. |
| remove obstruction. |
c. | Fan motor disconnected | c. | Check fan motor operation. |
| or malfunctioning. |
| and electrical connections. |
|
|
| back to compressor. Check |
|
|
| for 115VAC from compressor |
|
|
| to motor. Reconnect or repair |
|
| wires or replace motor if | |
|
|
| defective. |
|
|
| 9. | Compressor Fault |
|
|
|
|
| a. | Compressor electrical | a. | Check integrity of compressor |
|
|
|
| components disconnected |
| electrical components (See page |
|
|
|
| or malfunctioning. |
| 15 and 16). Check electrical |
|
|
|
|
|
| connections back to control |
|
|
|
|
|
| board. Replace defective com- |
|
|
|
|
|
| ponent or repair wiring. Check |
|
|
|
|
|
| for 115VAC from the control |
|
|
|
|
|
| board. Correct any wiring |
|
|
|
|
|
| problems or replace compressor |
|
|
|
|
|
| components if defective. If no |
|
|
|
|
|
| power from control board. |
|
|
|
|
|
| replace control board. |
|
|
| b. | Compressor inefficient | b. | For Compressor specifications, |
|
|
|
|
|
| electrical inputs and output |
|
|
|
|
|
| (See page 16). |
|
|
| c. | Compressor locked | c. | (See page 16). |
|
|
|
|
|
|
|
| B. Warm Temperature | 1. | Control Set too Warm | a. | Check | |
| in only one wine |
| 2. | Unit Recently Energized |
| points. |
|
|
|
| |||
| storage compartment. | a. | Allow time for unit to pull down. | |||
|
|
| 3. | Unit Recently Stocked | a. | Instruct customer |
|
|
|
| with Wine. |
|
|
|
|
|
|
|
|
|
|
|
| 4. | High Room Ambient | a. | Instruct customer that unit |
|
|
|
|
|
| performs best between 60°F / |
|
|
|
|
|
| 16°C |