Installation Instruction

Installation Instruction

Federal law requires that WINEMATE split cooling systems be installed by an EPA certified refrigeration technician.

1.Location

Place the condensing unit in a properly ventilated location. If it is not, heat exhausted by the condensing unit will build up and the cooling system will not operate properly.

Leave minimum 3 feet clearance between the exhaust side and the wall.

Leave minimum 1 foot clearance for the fresh air supply side.

Condensing unit should be elevated to avoid possible flooding and shaded from direct sun. It should not be exposed to temperatures higher than 125 °F or lower than 20 °F.

Air flow from the unit cooler should be unobstructed for at least 1 foot.

2.Refrigeration Installation

Model

Liquid Line Diameter

Suction Line Diameter

Pipe (inch)

 

(inch), recommended

(inch), recommended

 

 

 

 

 

WM-2500SSH

3/8

3/8

8

WM-4500SSH

3/8

3/8

8

WM-6500SSH

3/8

5/8

10

WM-8500SSH

3/8

5/8

10

WINEMATE split system is shipped as components and is ready for use only after a certified refrigeration technician has properly installed and tested the system. Proper installation is critical. WINEMATE can only warrant the quality of the components. The installation and proper operation of the system must be warranted by the installer.