Cord Connected Ovens

WARNING: THE ELECTRICAL CORD HAS A GROUNDING PLUG WHICH MUST BE CONNECTED TO A PROPERLY GROUNDED RECEPTACLE. IF THE RECEPTACLE IS NOT THE PROPER GROUNDING TYPE, CONTACT AN ELECTRICIAN. DO NOT REMOVE THE GROUNDING PRONG FROM THE PLUG.

ELECTRICAL DATA

 

 

 

 

 

 

 

 

 

 

 

Fuse

 

 

 

 

 

 

 

 

 

 

 

Circuit

Size or

90°

 

Volts / Hz

 

 

 

 

 

 

 

 

Circuit

Model

 

Kilowatts

 

 

Rated Amps

 

Size

Copper

/ Ph

 

 

 

 

Breaker

 

 

 

 

 

 

 

 

 

(Amps)

Wire Size

 

 

 

 

 

 

 

 

 

 

Size*

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(Amps)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CB1824E

208/60/1

 

9.4

 

 

45.2

 

 

60

60

6

 

 

 

 

 

 

 

 

 

 

 

 

 

CB1824E

240/60/1

 

9.4

 

 

39.2

 

 

50

50

8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Per Phase

 

 

Per Line Wire

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

L1 - L2

L2 - L3

L1 - L3

L1

 

L2

 

L3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CB1824E

208/60/3

5.2

1.6

2.6

32.5

 

28.3

 

17.5

40

40

8

 

 

 

 

 

 

 

 

 

 

 

 

 

CB1824E

240/60/3

5.2

1.6

2.6

28.2

 

24.5

 

15.2

40

40

8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

* Dual Element Time-Delay Fuse or

 

 

 

 

 

 

 

 

 

 

Inverse Time Circuit Breaker

 

 

 

 

 

 

 

 

 

 

 

 

 

Circuit Size (Minimum) & Fuse / Circuit Breaker Size (Maximum) compiled in accordance with the National Electrical Code (ANSI/ NFPA 70), 1993 Edition.