Vulcan-Hart VSP200, WSPR2 Installation Codes and Standards, GAS Pressure Regulator Installation

Models: ML-052823 ML-052822 VSP100 ML-760601 ML-769292 ML-760600 VSP200 VSP200F WSPR1 WSPR2F WSPR2

1 7
Download 7 pages 50.63 Kb
Page 4
Image 4

INSTALLATION CODES AND STANDARDS

The Stockpot Range must be installed in accordance with:

In the United States of America:

1.State and local codes.

2.National Fuel Gas Code, ANSI-Z223.1/NFPA #54 (latest edition). This shall include but not be limited to: NFPA #54 Section 10.3.5.2 for Venting. Copies may be obtained from The American Gas Association Accredited Standards Committee Z223, @ 400 N. Capital St. NW, Washington, DC 20001 or the Secretary Standards Council, NFPA, 1 Batterymarch Park Quincy, MA 02169-7471

NOTE: In the Commonwealth of Massachusetts

All gas appliances vented through a ventilation hood or exhaust system equipped with a damper or with a power means of exhaust shall comply with 248 CMR.

3.NFPA Standard # 96 Vapor Removal from Cooking Equipment, latest edition, available from the National Fire Protection Association, Batterymarch Park, Quincy, MA 02269.

In Canada:

1.Local codes.

2.CAN/CSA-B149.1 Natural Gas Installation (latest edition)

3.CAN/CSA-B149.2 Propane Installation Code (latest edition), available from the Canadian Gas Association, 178 Rexdale Blvd., Etobicoke, Ontario, Canada M9W 1R3

GAS PRESSURE REGULATOR INSTALLATION

Gas regulator pressure is preset at 5” Water Column (W.C.) for natural gas, and 10” W.C. for propane gas. Minor adjustments may be required based on site specific gas pressure.

Install the regulator as close to the stockpot on the gas supply line as possible. Make sure that the arrow on the underside of the regulator is oriented in the direction of gas flow to the stockpot (Fig. 2) and the regulator is positioned with the vent plug and adjustment screw upright (Fig. 3).

Fig. 2

Fig. 3

The minimum supply pressure (upstream of the regulator) should be 7-9” W.C. for natural gas and 11-12” W.C. for propane gas. At no time should the hotplate be connected to supply pressure greater than ½ psig (3.45 kPa) or 14” W.C.

- 4 -

Page 4
Image 4
Vulcan-Hart WSPR2F, WSPR1, VSP200F, ML-760600 Installation Codes and Standards, GAS Pressure Regulator Installation