Model LG & LD Pool and Spa Heater

Page 21

 

 

 

 

3H. Periodic Inspection

WARNING

Improper installation or maintenance can cause nausea or asphyxiation from carbon monoxide in flue gases which could result in severe injury, or death.

3H-1. Owner Inspection

Waterpik Laars designs and constructs the Laars Lite 2 heater to provide long performance life when installed and operated properly under normal condi- tions. The following basic guidelines are suggested for your inspection:

1.Keep the top and surrounding area of the heater clear of all debris.

2.Keep the heater area clean and free of all com- bustible materials, flammable liquids and vapors, as well as sanitization chemicals.

3.Do not use the heater if any part has been under water. Immediately call a qualified professional technician to inspect the heater and replace any part of the control system which has been sub- merged.

N'utilisez pas cet appareil s'il a été plongé dans l'eau, même partiellement. Faites inspecter l'appareil par un technicien qualifié et remplacez toute partie du système de contrôle et toute commande qui ont été plongés dans l'eau.

4.If the heater is equipped with a pressure relief valve, check for corrosion in and around the valve. With the filter pump on, lift the release lever on the top of the valve to make sure that water runs freely through it. If corrosion is found, replace the pressure relief valve. When replacing the valve, be sure that the pump is off. Install the valve so that the discharge is directed away from any area the may be damaged by water.

5.Be sure all combustion air and ventilation open- ings are not blocked.

3H-2. Professional Inspection

In addition, annual inspections by a qualified professional technician are recommended to keep the heater operating safely and efficiently through the years. The following basic checks should be performed.

1.Check for loose or broken wires and terminal connections.

2.Verify pressure switch operation by cycling the spa pump on and off a few times. The heater should go off immediately after the pump stops.

3.Inspect the electrical controls, specifically the following:

a.High limit controls.

b.Pressure switch.

c.Temperature control.

d.Automatic gas valve.

4.Inspect the venting system for blockage, leakage, and corrosion.

5.Check for spider webs in the pilot and main burner orifices - especially at Spring start-up.

6.Conduct a normal operating cycle and observe that the sequence proceeds as intended.

7.Inspect the external surfaces of the heat exchanger tubes for black carbon soot buildup by placing a mirror between and under the burners when the heater is firing. Remove any soot that has collected on the tubes, and correct the cause.

NOTE: After installation and first start-up, check the heat exchanger for black carbon soot buildup after the following periods of operation: 24 hours, 7 days, 30 days, 90 days, and once every 6 months thereafter.

Proper flames appear:

a.Blue in color.

b.1 to 4 inches (25 to 102mm) high above burner surface.

SECTION 4.

Parts List for Laars Lite 2 Heater

4A. General Information

To purchase parts or obtain a comprehensive maintenance manual for the Laars Lite 2 heater, contact your nearest Waterpik Laars dealer or distributor. If they cannot supply you with what you need, contact the Customer Service Manager, Waterpik Laars, 21 Pimentel Ct, Novato, California, 94949, Telephone (415) 382-8220 extension 245.

4B. Parts List

The following three pages contain a parts list, general exploded view and detailed exploded views to aid in parts identification. Please refer to these pages when ordering parts for your Laars Lite 2 pool heater.