Model LG & LD Pool and Spa Heater

Page 3

 

 

 

 

Notes:

1.An Underwriters' Laboratories listed vent cap is required to prevent downdraft and allow the heater to function properly and safely.

2.Use approved roof jack.

Figure 2. Indoor Installation Venting (USA), or Outdoor Shelter (Canada).

Table 1. Air Openings to Outside.

Required Net Free Open Area for Combustion Air Openings

 

Direct from outside

Duct from outside

 

 

 

 

 

Model

in2

(cm2)

in2

(cm2)

125

32

(206)

64

(413)

 

 

 

 

 

175

44

(284)

88

(568)

 

 

 

 

 

250

63

(406)

126

(813)

325

82

(429)

164

(1058)

 

 

 

 

 

400

100

(645)

200

(1290)

 

 

 

 

 

Note: If using screens and/or louvers, compensate by adding 50% additional area to each opening.

When a drafthood is used, it must be connected to a vent pipe which stops at least 2 feet (0.61 meters [m]) above the highest point of the roof or other object that is within 10 feet (3.05 m) from the vent termina- tion. The vent pipe must have a listed vent cap which allows a full equivalent opening for flue products (see Figure 2).

2C. Site Location

WARNING

Improper installation or maintenance can cause nausea or asphyxiation from carbon monoxide in flue gases which could result in severe injury, or death.

2C-1. Installation Information

Avoid placing the heater in locations where it can cause damage by water or condensate leakage. If this is not possible, provide a suitable drain pan to catch and divert any leakage. The pan must not block natural flow of air around the heater.

Locate the heater so the clearances from combus- tible surfaces shown in Table 2 are met.

Table 2. Minimum Heater Clearances From Combustible Surfaces

 

Indoor (Outdoor Shelter) Installation

 

Outdoors Installation

 

U.S.

 

 

Canada

 

U.S.

 

Canada

Side of Heater

inch

(cm )

inch

( cm )

inch

(cm )

inch

(cm )

Blank

6

(15.2 )

6

(15.2 )

6

( 32 )

6

(15.2 )

Rear

6

(15.2 )

6

(15.2 )

6

( 32 )

6

(15.2 )

Piping

12

(30.5 )

18

(45.7 )

12

(30.5)

18

(45.7 )

Top

44

(111.7 )

44

(111.7 )

 

Open Unroofed Area

Front

18

(45.7 )

36

(91.4 )

18

(45.7 )

36

(91.4 )

Page 5
Image 5
Waterpik Technologies LD, LG operation manual 2C. Site Location, 2C-1. Installation Information