230 Volt |
230 VAC CONVERTED SPA
Converted |
Sorrento® &
Trinidad®
Jumper
Configuration
SEE WIRING ILLUSTRATION
TERMINAL BLOCK
POWER JUMPER
REMOVE POWER JUMPER FROM TERMINAL BLOCK TO CONVERT SPA TO OPERATE AT 230 VAC.
NOTE: To change from Fahrenheit to Celsius remove jumper on JP2.
230Volt
Mallorca® &
La Palma Spa Model Jumper
Configuration
230 VAC PERMANENTLY CONNECTED SPA
NO POWER
JUMPERS REQUIRED
SEE WIRING
ILLUSTRATION
NOTE: To change from Fahrenheit to Celsius remove jumper on JP2.
230 VOLT SUBPANEL WIRING INSTRUCTIONS
NOTE: The subpanel must be placed within 100 feet of the main electrical service panel, and between 5 (1.5 m) and 50 feet (15 m) away from the spa. All electrical connections must be made in accordance with the wiring information contained in this manual and on the back of the field wiring access panel of the control box.
Refer to the wiring diagram below.
1.Connect the #8 AWG, WHITE [NEUTRAL] wire from the Neutral/Ground Bar on the main electrical service to the WHITE [NEUTRAL, Panel Neutral, Pigtail] of the subpanel.
2.Connect the #8 AWG, BLACK [L1] wire from the main electrical service to the subpanel [terminal L1].
3.Connect the #8 AWG, RED [L2] wire from the main electrical service to the subpanel [terminal L2].
4.Connect the #8 AWG, GREEN wire from the Neutral/Ground Bar on the main electrical service to the GROUND terminal of the subpanel.
5.Connect the #8 AWG, WHITE [NEUTRAL] wire from the subpanel breaker to the Neutral terminal on the spa’s control box.
6.Connect the #8 AWG, BLACK [L1] wire from the subpanel breaker to terminal [L1] on the spa’s control box.
7.Connect the #8 AWG, RED [L2] wire from the subpanel breaker to terminal [L2] on the spa’s control box.
8.Connect the #8 AWG, GREEN wire from the GROUND terminal of the subpanel to the GROUND terminal in the spa’s control box.
9.Bond the spa to all exposed metal equipment or fixtures, handrails, and concrete pad pre N.E.C. and all local codes.
| PERMANENTLY CONNECTED |
230VAC, 50 AMP | 230 VAC, 40A, 60Hz, MODELS |
| |
CIRCUIT BREAKER |
|
(NON GFCI) |
|
#8 AWG WHITE, NEUTRAL
#8* AWG GREEN, GROUND #8 AWG BLACK, L1
#8 AWG RED, L2
MAIN SERVICE |
|
| |
ELECTRICAL |
| ||
PANEL | LESS THAN 100 FT. | ||
WITH GFCI | |||
| |||
|
| BREAKERS |
N, NEUTRAL, #8 AWG WHITE
L2, HOT, #8 AWG RED
L1, HOT, #8 AWG BLACK
GROUND, #8 AWG GREEN*
MORE THAN 5 FEET
THE
CONTROL BOX
* A L L C A N A D I A N S PA M O D E L S U S E # 8 AW G G R E E N , G R OU N D . THESE SPAS ARE INTENDED FOR USE WITH GFCI SUBPANEL PROVIDED.
Page 6 | Electrical Installation |
|
|