Wayne CDUCAP Series Notas, Maintenance, Troubleshooting Chart, Symptom, Possible Causes, 18-Sp

Models: CDUCAP Series

1 10
Download 10 pages 24.74 Kb
Page 3
Image 3
Notas

Manual de Instrucciones de Operación y Piezas

CDUCAP Series

Notas

Maintenance

Always disconnect the electrical supply

before attempting to install, service, relocate or perform any maintenance. If the power source is out of sight, lock and tag in the open (off) position to prevent unexpected power application. Failure to do so could result in fatal electrical shock. Only qualified electricians should repair this unit. Improper repair could result in fatal electrical shock.

1 . Let the pump cool for a minimum of two hours before servicing because the pump contains hot oil under pressure and the motor is hot.

2 . Disassembly of the motor prior to expiration of warranty will void the warranty. If repairs are required, see troubleshooting chart.

3 . Inlet should be kept clean and free of all foreign objects and inspect annually. A clogged inlet will damage pump.

4 . Pump should be checked monthly for proper operation. Pump can be checked for proper operation by briefly removing pump power cord from the back of the water sensor plug and inserting directly into the

grounded outlet. In this condition, the pump will run continuously. Once pump operation is verified, replace pump power cord into the back of the water sensor plug (see Figure 2).

5 . Wipe water sensor surface regularly to prevent silt or other coatings from building up on sensor face (see Figure 2).

This pump contains dielectric oil for

cooling. This oil can be harmful to the environment. Check the state environmental laws before disposing this oil.

18-Sp

Troubleshooting Chart

Symptom
Possible Cause(s)
Corrective Action

 

 

 

Pump will not start or

1. Blown fuse

1. If blown, replace with proper sized fuse or reset breaker

run

2. Low line voltage

2. If voltage is under 108 volts, check wiring size

 

3. Defective motor

3. Replace pump

 

4. Impeller

4. If impeller will not turn, remove housing and remove

 

 

blockage

 

 

 

Pump starts and stops

1. Backflow of water from

1. Install or replace check valve

too often

piping

 

 

2. Incoming water is draining

2. Position pump switch away from the inlet so switch is clear

 

on sensor face

from incoming water (see Figure 1)

 

 

 

Pump will not shut

1. Obstacle in piping

1. Remove pump and clean pump and piping

off or thermal

2. Low Line Voltage

2. If voltage is under 108 volts, check wiring size

protector turns off

3. Too many appliances on

3. Install pump on dedicated circuit. IMPORTANT: Do not use

 

circuit

extension cord to power pump.

 

4. Dirty water sensor

4. Clean sensor face (see Figure 2)

 

5. Incoming water is draining

5. Position pump switch away from the inlet so switch is clear

 

on sensor face

from incoming water (see Figure 1)

 

 

 

Pump operates but

1. Plugged impeller

1. Clean out impeller

delivers little or no

2. Check valve installed

2. Reverse position of check valve

water

backwards

 

 

3. Pump airlocked

3. Drill 1/8” hole in discharge line between pump and check

 

 

valve

 

 

 

Gurgling sound from

1. Air injested into pump

1. Wipe off surface of sensor (see Figure 2)

pump at end of cycle

2. Time required for

2. Additional run time will not damage pump

 

pumping is less than 4

 

 

seconds

 

w w w .waynepumps. c o m

3

Page 3
Image 3
Wayne CDUCAP Series Notas, Maintenance, Troubleshooting Chart, Symptom, Possible Causes, Corrective Action, 18-Sp