12 | GAS INSTRUCTIONS |
|
INSTALL GAS SUPPLY
General Specifications for Piping
Note - Contact your local municipality for building codes regulating outdoor gas fireplace installations.
•Refer to AS5601 gas installations for piping and hose requirements.
•Refer to AS5601/AG 601, local authority, gas, electric, and other relevant statutory regulations for use and installation.
•WE RECOMMEND THAT THIS INSTALLATION BE DONE BY A PROFESSIONAL.
Some of the following are general requirements taken from the latest edition of the National Fuel Gas Code: ANSI Z 223.1/NFPA 54, or CAN/
•This fi replace is designed to operate at 4 inches of water column pressure (.2526 psi).
•The maximum inlet gas pressure for this fi replace is 7 inches of water column pressure.
•A manual
•An additional manual
•The quick disconnect connects to a 3/8 inch NPT thread from the gas source. The quick disconnect fi tting is a
fi replace is disconnected.
•The quick disconnect fi tting can be installed horizontally, or pointing downward. Installing the fi tting with the open end pointing upward can result in collecting water and debris.
•The dust covers (supplied plastic plugs) help keep the open ends of the quick disconnect fi tting clean while disconnected.
•Pipe compound should be used which is resistant to the action of natural gas when connections are made.
•The outdoor connector must be fi rmly attached to rigid, permanent construction.
WARNING: Do not route the 10 foot hose under a deck. The hose must be visible.
Gas Line Piping
•If the length of the line required does not exceed 50 feet, use a 5/8" O.D. tube. One size larger should be used for lengths greater than 50 feet.
•Gas piping may be copper tubing, type K or L; polyethylene plastic tube, with a minimum wall thickness of .062 inch; or standard weight (schedule 40) steel or wrought iron pipe.
•Copper tubing must be
•Plastic tubing is suitable only for outdoor, underground use.
•Gas piping in contact with earth, or any other material which may corrode the piping, must be protected against corrosion in an approved manner.
•Underground piping must have a minimum of 18" cover.
•Installation and repair should be done by a qualifi ed service person. The fi replace should be inspected before use and at least annually by a qualifi ed service person. More frequent cleaning may be required as necessary. It is imperative that control compartment, burners and
circulating air passageways of the fi replace be kept clean.
Test Connections
All connections and joints must be thoroughly tested for leaks in accordance with local codes and all listed procedures in the latest edition of the National Fuel Gas Code: ANSI Z 223.1/NFPA 54, or
Gas supply
Inside wall
Outside wall Shut off
This is a typical installation of a Weber® natural gas fireplace. Local codes may require different installations.
Locking shut off
Quick | 3/ " Pipe | 1/ " Pipe |
disconnect | 8 | 2 |
nipple | nipple |
Do Not Use