| GAS INSTRUCTIONS | 15 | |
|
|
| |
Check: |
|
| |
1) | Bulkhead fi |
| (1) |
| WARNING: If there is a leak at connections (1), turn |
|
|
| OFF the gas. DO NOT OPERATE THE FIREPLACE. |
|
|
| Contact the Customer Service Representative in your |
|
|
| area using the contact information on our web site. |
|
|
| Log onto www.weber.com®. |
|
|
2) |
|
| |
3) |
| (2) | |
4) Test point fi tting |
|
| |
| WARNING: The test point fitting should only be |
|
|
| loosened or removed by an authorized service person. |
|
|
5) Quick |
|
| |
| WARNING: If there is a leak at connection (2), (3), (4) |
|
|
| or (5), retighten the fitting by hand. Make sure the |
|
|
| quick disconnect fittings are properly seated. Recheck |
|
|
| for leaks with soap and water solution. If a leak |
| (3) |
| persists after these measures, turn OFF the gas. DO |
|
|
| NOT OPERATE THE FIREPLACE. Contact the Customer |
|
|
| Service Representative in your area using the contact |
|
|
| information on our web site. Log onto www.weber.com®. |
|
|
When leak checks are complete, turn gas supply OFF at the source and |
|
| |
| rinse connections with water. | (5) | (4) |
|
|
Table | Maximum Capacity of Pipe in Cubic Feet of Gas per Hour for Gas Pressures of 0.5 psi or Less and a Pressure Drop of 0.3 Inch |
| ||||||||||||||
|
|
|
| Water Column. (Based on a 0.60 Specific Gravity Gas) |
|
|
|
|
| |||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
Nominal | Internal |
|
|
|
|
|
| Length of Pipe (Feet) |
|
|
|
|
|
|
| |
Iron Pipe | Diameter |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
Size | (Inches) | 10 | 20 | 30 | 40 | 50 | 60 | 70 | 80 | 90 | 100 | 125 | 150 | 175 | 200 |
|
(Inches) |
|
| ||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
1/4 | .364 | 32 | 22 | 18 | 15 | 14 | 12 | 11 | 11 | 10 | 9 | 8 | 8 | 7 | 6 |
|
3/8 | .493 | 72 | 49 | 40 | 34 | 30 | 27 | 25 | 23 | 22 | 21 | 18 | 17 | 15 | 14 |
|
1/2 | .622 | 132 | 92 | 73 | 63 | 56 | 50 | 46 | 43 | 40 | 38 | 34 | 31 | 28 | 26 |
|
3/4 | .824 | 278 | 190 | 152 | 130 | 115 | 105 | 96 | 90 | 84 | 79 | 72 | 64 | 59 | 55 |
|
1 | 1.049 | 520 | 350 | 285 | 245 | 215 | 195 | 180 | 170 | 160 | 150 | 130 | 120 | 110 | 100 |
|
1 1/4 | 1.380 | 1050 | 730 | 590 | 500 | 440 | 400 | 370 | 350 | 320 | 305 | 275 | 250 | 225 | 210 |
|
1/12 | 1.160 | 1600 | 1100 | 890 | 760 | 670 | 610 | 560 | 530 | 490 | 460 | 410 | 380 | 350 | 320 |
|
2 | 2.067 | 3050 | 2100 | 1650 | 1450 | 1270 | 1150 | 1050 | 990 | 930 | 870 | 780 | 710 | 650 | 610 |
|
2 1/2 | 2.469 | 4800 | 3300 | 2700 | 2300 | 2000 | 1850 | 1700 | 1600 | 1500 | 1400 | 1250 | 1130 | 1050 | 980 |
|
3 | 3.068 | 8500 | 5900 | 4700 | 4100 | 3600 | 3250 | 3000 | 2800 | 2600 | 2500 | 2200 | 2000 | 1850 | 1700 |
|
4 | 4.026 | 17500 | 12000 | 9700 | 8300 | 7400 | 6800 | 6200 | 5800 | 5400 | 5100 | 4500 | 4100 | 3800 | 3500 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
© 1997 National Fire Protection Association, Inc,. and International Approval Services - U.S., Inc. All Rights Reserved.