10a Service and maintenance — schedule

GOLD CGs Gas-Fired Water Boiler — Boiler Manual VERIFY PROPER OPERATION AFTER SERVICING

10a Service and maintenance — schedule

VERIFY PROPER OPERATION AFTER SERVICING

Table 5 Service and maintenance schedules

Service technician

(see following pages for instructions)

 

Inspect:

 

• Reported problems

 

Boiler area

 

Air openings

 

Flue gas vent system (and air piping)

 

Pilot and main burner flames

 

Water piping

 

Boiler heating surfaces

 

Burners, base and inlet air box

UP

• Condensate drain system

-

 

 

TART

Service:

 

S

Inducer motor

 

 

ANNNUAL

Oiled-bearing circulators

 

 

Start-up:

 

Perform start-up per manual

 

Check/test:

 

• Gas piping

 

Cold fill and operating pressures

 

Air vents and air elimination

 

Limit controls and cutoffs

 

• Expansion tank

 

Boiler relief valve

 

Review:

 

• Review with owner

 

 

 

Owner maintenance

(see CGs User’s Information Manual for instructions)

 

Check boiler area

Daily

Check air openings

 

 

 

Check boiler pressure/

 

 

temperature gauge

 

 

 

 

Check boiler interior piping

 

• Check venting system

 

Check air vents

Monthly

Check boiler relief valve

 

 

• Check condensate drain system

 

Check automatic air vents (if

 

 

used)

 

 

 

 

Test low water cutoff (if used)

Periodically

Clean vent termination/air intake

 

 

 

screens

 

 

 

Every 6 months

Oil inducer motor

Operate relief valve

 

 

 

 

End of season • Shut down procedure

Follow the Service and maintenance procedures given throughout this manual and in com- ponent literature shipped with the boiler. Failure to perform the service and maintenance could result in damage to the boiler or system. Failure to follow the directions in this manual and component literature could result in severe personal injury, death or substantial property damage.